| 2014-07-01 07:22:52 | BUILDING PLAN REVIEW |
| | PERMIT: 14060286 |
| | ADD: 1220 ORTEGA RD |
| | CONT: WILBUR HOBGOOD CONST. |
| | TEL: (561)691-9686 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: JULY 01/ 2014 |
| | ACTION: DENIED |
| | |
| | 1) INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE |
| | INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | 2) SHEET A-5: |
| | 2A) 2010 FBC-B 1008.1.6 OR 1009.5 STAIRWAY LANDINGS. |
| | THE RIGHT SIDE OF THE SHEET DOORWAY FROM STORAGE THE |
| | DOOR SWINGS OUT OVER THE STAIRS FROM SHEET A2 THE |
| | LANDING APPEARS TO HAVE BEEN LENGHTENED BUT NOT TO CODE |
| | COMPLIANCE. THE OTHER ISSUE WITH THIS STAIR IS THAT IT |
| | MAY NOT REGUIRE A GAURDRAIL THESE STAIRS DO REQUIRE A |
| | HANDRAIL PER SECTION 2010 FBC-B 1009.12. |
| | |
| | 2B) THE NEW ACCESS RAMP SHOWS A FOOTER DETAIL SHEET A7 |
| | AS (F4) THIS DETAIL SHOWS EDGE PROTECTION BUT NOT A |
| | HANDRAIL NOR GAURD RAIL AS REQUIRED BY FBC-B 1010.8 AND |
| | 1010.10. NOTE FLOOR ELEVATIONS IN REGARDS TO GRADE ARE |
| | NOT GIVEN. THE EXISING STAIR HAS 6 RISERS @ 7 IN= 42 |
| | INCHES IN HEIGHT. NOTE SHEET A6 SHOWS THE NEW |
| | ACCESSIBLE RAMP AT A LOWER LEVEL THAN THE EXISTING |
| | STRUCTURE WHERE AS SHEET A7 FOOTER DETAIL F2 SHOWS THE |
| | FLOORS AT THE SAME LEVEL. DISCREPANCY IN PLANS. |
| | |
| | 2C) THE NEW ACCESSIBLE RESTROOM DOES NOT MEET THE |
| | ACCEESSIBLE RESTROOMDIMENSIONAL REQUIREMENTS. THERE IS |
| | A DISCREPANCY IN THE PLANS SHEET A5 SHOWS A DIMENTION |
| | OF 6'-10" SHEET DETAIL ON SHEET A9 SHOWS THIS SAME WALL |
| | 5'-9". THE MINIMUM DIMENSION FOR THE FIXTURE SET WALL |
| | IS 7'-01/2". 2010 FBC- ACCESSIBILITY CODE 604.2 & |
| | 604.3.2 & FIGURE 604.8.1.6. |
| | |
| | |
| | 3) SHEET A7 PLEASE REVIEW BEAM TAG C, IS THIS BEAM 84 |
| | INCHES DEEP OR IS THIS A TYPO? 107.2.1.3. ADITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 4) SHEET A-8 ADDITIONAL INFORMATION REQUIRED A8 VERSES |
| | A6, THE PLANS DO NOT PROVIDE EITHER AN INTERMEDIATE TIE |
| | BEAM OR LINTEL. |
| | 5 DOORS ARE DRAWN TO A 7'-0" ELEVATION |
| | 1 DOOR IS INDICATED TO BE AT ELEVATION 10'-0" TOP OF |
| | BEAM |
| | ROOF ELEVATION IS INDICATED AT 12'-0" TOP OF BEAM OR |
| | 12'-9" APPPROX. |
| | SECTION THROUGH ROOF A-8 MIN ABOVE 14'-0" ABOVE |
| | LANDING, THERE IS A DISCREPANCY IN THE DETAIL AND |
| | ELEVATION SHEET A6. |
| | |
| | 5) 2010 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE |
| | CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL |
| | IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO |
| | THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING |
| | OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A |
| | GEOTECHNICAL INVESTIGATION BE CONDUCTED. |
| | |
| | 6A) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6B) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) |
| | SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT |
| | WILL REQUIRE PRODUCT APPROVALS: |
| | MISSING REPORTS: |
| | (31)(B) WINDOW REPORT ONLY COVER SHEET SUBMITTED. |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 7) NO MEP PLANS SUBMITTED!!! OLD SHEETS SHEET SHEET M-1 |
| | INDICATE THE USE OF ROOF STANDS, M2 INDICATES THE ROOF |
| | STANDS BEING TIED DOWN TO A CONCRETE DECK PLEASE |
| | PROVIDE LOCATION OR ARE THEY BEING PLACED ON THE NEW |
| | WOOD DECKS? ADDITIONAL INFORMATION REQUIRED. 107.2.1.3. |
| | |
| | 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |