| 2014-06-30 17:03:28 | DATE: 6/30/2014 |
| | PROJECT: ERNESTON |
| | PERMIT#: 14060236 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | THE ADDITION INDICATES NO ELECTRICAL WORK AT ALL. BUT |
| | THE FLOOR PLAN INDICATES THE INSTALLATION OF NEW OFFICE |
| | AND BATHROOM AREAS. |
| | |
| | 1) CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. FBC 107.2.1 |
| | |
| | 2) INDICATE ALL LIGHTS AND RECEPTACLE OUTLETS PROPOSED |
| | FOR THE NEW CONSTRUCTION AREA. FBC 107.2.1 |
| | |
| | 3) A SWITCHED LIGHT OUTLET IS REQUIRED AT THE ATTIC |
| | ENTRANCE. FBC 306.3.1 |
| | |
| | 4) AN ILLUMINATED MEANS OF EGRESS SHALL BE PROVIDED FOR |
| | ALL BUILDINGS OR STRUCTURES REQUIRED IN CHAPTERS 11 |
| | THROUGH 43. NFPA 101 SECTION 7.9 |
| | |
| | 5) MEANS OF EGRESS SHALL BE MARKED WHERE REQUIRED IN |
| | CHAPTERS 11 THROUGH 43. NFPA 101 SECTION 7.10 |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |