| Plan Review Notes For Permit 14060284 |
| Permit Number |
14060284 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-05 13:56:07 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. PLAN SHOULD INCLUDE: | | | | | | PRINTED NAME AND SIGNATURE OF THE INDIVIDUAL TAKING | | | RESPONSIBILITY FOR THE DESIGN, FBC 107. | | | | | | WIND DESIGN CRITERIA FBC 1603.4.1. | | | | | | 2. IF PLANS ARE NOT SIGNED AND SEALED BY A DESIGN | | | PROFESSIONAL, PROVIDE CALCULATIONS. IT IS NOT CLEAR | | | WHETHER OR NOT THE 2' EMBEDMENT WITH CONCRETE IS | | | ADEQUATE FOR AN 8' HIGH SIGN. | | | | | | 3. REVISE PLANS TO SHOW SIGN CONSTRUCTION. NO | | | INFORMATIN REGARDING FASTENERS, BACKING WERE PROVIDED. | | | |
|