Plan Review Notes
Plan Review Notes For Permit 14060247
Permit Number 14060247
Review Stop B
Sequence Number 1
Notes
Date Text
2014-07-01 14:33:57RESIDENTIAL (R2) ALTERATION/ADDITION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- SHEET A-2:
 A) ENGINEER TO CORRECT ALL THE CODE INFORMATION. *THIS
 IS A MULTIFAMILY RESIDENTIAL BUILDING WITH 4 UNITS
 (R2). THIS IS NOT AN ENCLOSED SINGLE FAMILY ADDITION,
 THEREFORE, THE FLORIDA RESIDENTIAL CODE DOESN'T APPLY.
 ** THIS IS NOT R3 OCCUPANCY. *** THIS IS NOT AN
 ALTERATION LEVEL 2. SEE CHAPTER 4 OF FBC-EXISTING
 BUILDING AND IDENTIFY CORRECT ALTERATION LEVEL. ALSO,
 CONSIDER THAT THERE IS AN ADDITION SHOWN ON THE PLANS
 SUBMITTED. REVISE ALL THE INFORMATION AS REQUIRED.
  
 B) ENGINEER TO PROVIDE COMPLETE FRAMING DETAILS AND
 SPECIFICATIONS FOR THE NEW PROPOSED ENTRY DOOR AND THE
 NEW PROPOSED SLIDING GLASS DOORS (INCLUDING THE DOOR
 STRUCTURAL BUCK INFORMATION) . SEC. 1403.3 AND SEC.
 1715.5.4 OF 2010 FBC.
  
 2- ENGINEER TO REVISE THE BALCONY GUARDRAIL HEIGHT
 SPECIFICATIONS ON ALL FLOOR PLANS AND ELEVATIONS.
 MINIMUM HEIGHT IS 42" AS REQUIRED BY SEC. 1013.2 OF
 2010 FBC.
 ***NOTE: TAKE THIS HEIGHT IN CONSIDERATION AT THE NEW
 ENTRY AREA WHERE 2 NEW STEPS WERE ADDED TO ALLOW FOR
 THE COVERED ENTRY HEADROOM CLEARANCE ON FIRST FLOOR.
  
 3- ENGINEER TO PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR THE WEATHER PROTECTION OF THE ROOF
 DECK (BALCONY) AS REQUIRED BY SEC. 1503 OF 2010 FBC.
 SPECIFY DECK APPROVED COVERING, FLASHING, DRAINAGE AND
 SECONDARY EMERGENCY DRAINS OR SCUPPERS.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) THE ROOF DECK APPROVED COVERING. NOTE: COORDINATE
 WITH ITEM # 3 ABOVE.
  
 B) ENTRY DOOR. PROVIDE COMPLETE DRAWINGS FOR FLORIDA
 PRODUCT APPROVAL FL16537 SUBMITTED. NO DRAWINGS
 SUBMITTED THIS TIME
  
 C) HORIZONTAL SLIDING WINDOWS. PROVIDE COMPLETE
 DRAWINGS. DRAWINGS ON NOA 12-0127.08 SUBMITTED ARE
 SPLICED IN DIFFERENT PAGES, THEREFORE, ARE NOT
 READABLE. SUBMIT COMPLETE DRAWINGS.
  
 D) FIXED WINDOWS. NOA 12-0307.06 SUBMITTED. SAME
 COMMENT AS ABOVE. NEED COMPLETE DRAWINGS.
  
 E) SLIDING GLASS DOORS. NOA 12-1204.12 SUBMITTED. SAME
 COMMENT AS ABOVE. NEED COMPLETE DRAWINGS.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712