| Plan Review Notes For Permit 14060242 |
| Permit Number |
14060242 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-07-16 11:00:58 | RESIDENTIAL (R3) REVISION, SECOND BUILDING REVIEW | | | CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- NEW COMMENT: | | | FLOOR PLAN WAS REVISED AGAIN SHOWING A NEW DOUBLE | | | FRENCH DOOR. PROVIDE COMPLETE FRAMING DETAIL AND | | | SPECIFICATIONS FOR THE NEW DOUBLE FRENCH DOOR AS | | | REQUIRED TO MEET THE DESIGN PRESSURES OF SEC. R301 OF | | | 2010 FBC-RESIDENTIAL. | | | | | | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR THE NEW DOUBLE FRENCH DOORS AS SHOWN | | | ON NEW REVISED PLAN. | | | | | | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE | | | PRODUCT APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY | | | AMENDMENTS TO FBC. | | | | | | 4- SECTION B ON SHEET A-3: REVISE ROOF SHEATHING | | | SPECIFICATIONS TO COMPLY WITH SEC. R803.2.3.1 OF 2010 | | | FBC-RESIDENTIAL. NEED TO SPECIFY 8D RING SHANK NAILS | | | AND FASTENER SPACING NEEDS TO BE AT 4" O.C. IN NAILING | | | ZONE #3. | | | | | | *** REVISED SECTION SUBMITTED STILL DOESN'T SPECIFY THE | | | "RING SHANK" NAILS. REVISE SPECIFICATIONS AS REQUIRED | | | | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | |
|