2014-07-16 11:00:58RESIDENTIAL (R3) REVISION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- NEW COMMENT:
 FLOOR PLAN WAS REVISED AGAIN SHOWING A NEW DOUBLE
 FRENCH DOOR. PROVIDE COMPLETE FRAMING DETAIL AND
 SPECIFICATIONS FOR THE NEW DOUBLE FRENCH DOOR AS
 REQUIRED TO MEET THE DESIGN PRESSURES OF SEC. R301 OF
 2010 FBC-RESIDENTIAL.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE NEW DOUBLE FRENCH DOORS AS SHOWN
 ON NEW REVISED PLAN.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE ABOVE
 PRODUCT APPROVAL AS REQUIRED BY SEC. 107.3.4.1 OF CITY
 AMENDMENTS TO FBC.
  
 4- SECTION B ON SHEET A-3: REVISE ROOF SHEATHING
 SPECIFICATIONS TO COMPLY WITH SEC. R803.2.3.1 OF 2010
 FBC-RESIDENTIAL. NEED TO SPECIFY 8D RING SHANK NAILS
 AND FASTENER SPACING NEEDS TO BE AT 4" O.C. IN NAILING
 ZONE #3.
  
 *** REVISED SECTION SUBMITTED STILL DOESN'T SPECIFY THE
 "RING SHANK" NAILS. REVISE SPECIFICATIONS AS REQUIRED
  
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
  