2014-07-16 14:12:20RESIDENTIAL (R3) REVISION, MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC
  
 1- A) PROVIDE REVISED EQUIPMENT SIZING CALCULATIONS
 SHOWING THE NEW PROPOSED EQUIPMENT MANUFACTURER AND
 MODEL NUMBER ALONG WITH THE SENSIBLE AND TOTAL COOLING
 CAPACITIES AS REQUIRED BY SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 B) PROVIDE THE PUBLISHED EQUIPMENT AHRI PAGE THAT
 MATCHES THE EQUIPMENT SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 403.6
  
 2- SPECIFY THE EQUIPMENT MANUFACTURER AND MODEL NUMBER
 ON PLANS PLANS AS REQUIRED BY SEC. 107.3.5.3 OF CITY
 AMENDMENTS TO FBC.
  