Plan Review Notes
Plan Review Notes For Permit 14060242
Permit Number 14060242
Review Stop B
Sequence Number 1
Notes
Date Text
2014-06-11 17:58:50RESIDENTIAL (R3) REVISION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
  
 A) NEW METAL ROOF AS SHOWN ON PLANS.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS. ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR.
  
 C) PEEL AND STICK UNDERLAYMENT SUITABLE FOR METAL
 ROOFING AS SPECIFIED ON PLANS.
  
 2- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL THE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC.
  
 3- SECTION B ON SHEET A-3:
 A) REVISE ROOF SHEATHING SPECIFICATIONS TO COMPLY WITH
 SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL. NEED TO
 SPECIFY 8D RING SHANK NAILS AND FASTENER SPACING NEEDS
 TO BE AT 4" O.C. IN NAILING ZONE #3.
  
 B) STUCCO TO BE 7/8" THICKNESS. TABLE R702.1(1).
  
 C) NEED TWO LAYERS OF APPROVED WATER-RESISTANT VAPOR
 BARRIER AS REQUIRED BY SEC. R703.6.3
  
 4- NEED SEPARATE ROOFING PERMIT. ROOFING CONTRACTOR
 REQUIRED. SEC. 489.113(3)(B) FLORIDA STATUTES.
  
 ***PROVIDE RESPONSE LETTER ADDRESSING EACH COMMENT TO
 EXPEDITE THE REVIEW PROCESS.
  