| 2014-08-27 15:01:25 | DATE: 7/9/2014 |
| | PROJECT: AMG PHILLIPS POINT EXPANSION |
| | PERMIT#: 14060196 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | 1) BOXES, CONDUIT BODIES, AND HANDHOLE ENCLOSURES SHALL |
| | BE INSTALLED SO THAT THE WIRING CONTAINED IN THEM CAN |
| | BE RENDERED ACCESSIBLE WITHOUT REMOVING ANY PART OF THE |
| | BUILDING OR, IN UNDERGROUND CIRCUITS, WITHOUT |
| | EXCAVATING SIDEWALKS, PAVING, EARTH, OR OTHER SUBSTANCE |
| | THAT IS TO BE USED TO ESTABLISH THE FINISHED GRADE. NEC |
| | 314.29. THE POWER PACKS FOR MOTION SENSORS APPEAR TO BE |
| | LOCATED IN AREAS WITH DRYWALL CEILINGS. ALL |
| | TRANSFORMERS, LED DRIVERS JUNCTION BOXES, POWER PACK |
| | AND THE LIKE SHALL BE INSTALLED SO AS TO REMAIN |
| | ACCESSIBLE AFTER INSTALLATION AND CONSTRUCTION IS |
| | COMPLETE. |
| | |
| | 2) PROVIDE PRODUCT APPROVALS FOR ALL FIXTURES. LISTING |
| | AND LABELING REQUIRED BY AN APPROVED TESTING LAB. IN |
| | JUDGING EQUIPMENT, CONSIDERATION SUCH AS THE FOLLOWING |
| | SHALL BE EVALUATED: SUITABILITY FOR INSTALLATION AND |
| | USE IN CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC |
| | 110.3(A)(1 THRU 8) |
| | |
| | 3) PROVIDE PRODUCT APPROVALS AND CUT SHEETS FOR FLOOR |
| | BOXES TO SHOW CODE COMPLIANCE WITH FIRE RATING FROM |
| | FLOOR TO FLOOR. ADDITIONAL INFORMATION REQUIRED. FBC |
| | 107.2.1.3 |
| | |
| | 4) PROVIDE MANUFACTURER DATA SHEETS ON THE CEO |
| | ELEVATOR. |
| | |
| | 5) WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF SERVICE |
| | FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE AHJ |
| | SHALL BE NOTIFIED, AND THE BUILDING SHALL BE EVACUATED |
| | OR AN APPROVED FIRE WATCH SHALL BE PROVIDED FOR ALL |
| | PARTIES LEFT UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE |
| | ALARM SYSTEM HAS BEEN RETURNED TO SERVICE. |
| | [101:9.6.1.6] NFPA-1, CHAPTER 13 SECTION 13.7.1.4.4 |
| | |
| | 6) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, PLANS, AND SHOP |
| | DRAWINGS AS REQUIRED FOR, FIRE ALARM, SECURITY, ACCESS |
| | CONTROL, CCTV, DATA/COM, NETWORK, STRUCTURED CABLING, |
| | AUDIO/VIDEO, AND SIGNAGE. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |