Plan Review Notes
Plan Review Notes For Permit 14060196
Permit Number 14060196
Review Stop E
Sequence Number 3
Notes
Date Text
2014-08-27 15:01:25DATE: 7/9/2014
 PROJECT: AMG PHILLIPS POINT EXPANSION
 PERMIT#: 14060196
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 3RD ELECTRICAL PLAN REVIEW
 ACTION: PROVISO
  
 1) BOXES, CONDUIT BODIES, AND HANDHOLE ENCLOSURES SHALL
 BE INSTALLED SO THAT THE WIRING CONTAINED IN THEM CAN
 BE RENDERED ACCESSIBLE WITHOUT REMOVING ANY PART OF THE
 BUILDING OR, IN UNDERGROUND CIRCUITS, WITHOUT
 EXCAVATING SIDEWALKS, PAVING, EARTH, OR OTHER SUBSTANCE
 THAT IS TO BE USED TO ESTABLISH THE FINISHED GRADE. NEC
 314.29. THE POWER PACKS FOR MOTION SENSORS APPEAR TO BE
 LOCATED IN AREAS WITH DRYWALL CEILINGS. ALL
 TRANSFORMERS, LED DRIVERS JUNCTION BOXES, POWER PACK
 AND THE LIKE SHALL BE INSTALLED SO AS TO REMAIN
 ACCESSIBLE AFTER INSTALLATION AND CONSTRUCTION IS
 COMPLETE.
  
 2) PROVIDE PRODUCT APPROVALS FOR ALL FIXTURES. LISTING
 AND LABELING REQUIRED BY AN APPROVED TESTING LAB. IN
 JUDGING EQUIPMENT, CONSIDERATION SUCH AS THE FOLLOWING
 SHALL BE EVALUATED: SUITABILITY FOR INSTALLATION AND
 USE IN CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC
 110.3(A)(1 THRU 8)
  
 3) PROVIDE PRODUCT APPROVALS AND CUT SHEETS FOR FLOOR
 BOXES TO SHOW CODE COMPLIANCE WITH FIRE RATING FROM
 FLOOR TO FLOOR. ADDITIONAL INFORMATION REQUIRED. FBC
 107.2.1.3
  
 4) PROVIDE MANUFACTURER DATA SHEETS ON THE CEO
 ELEVATOR.
  
 5) WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF SERVICE
 FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE AHJ
 SHALL BE NOTIFIED, AND THE BUILDING SHALL BE EVACUATED
 OR AN APPROVED FIRE WATCH SHALL BE PROVIDED FOR ALL
 PARTIES LEFT UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE
 ALARM SYSTEM HAS BEEN RETURNED TO SERVICE.
 [101:9.6.1.6] NFPA-1, CHAPTER 13 SECTION 13.7.1.4.4
  
 6) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, PLANS, AND SHOP
 DRAWINGS AS REQUIRED FOR, FIRE ALARM, SECURITY, ACCESS
 CONTROL, CCTV, DATA/COM, NETWORK, STRUCTURED CABLING,
 AUDIO/VIDEO, AND SIGNAGE.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  