Plan Review Notes
Plan Review Notes For Permit 14060196
Permit Number 14060196
Review Stop P
Sequence Number 2
Notes
Date Text
2014-07-26 11:06:39PLUMBING PLAN REVIEW
 PERMIT: 14060196
 ADD:777 S FLAGLER 12TH FLOOR
 CONT: WOOLEMS
 TEL: (561)835-0401
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SAT. JULY 26/2014
 ACTION: DENIED
  
 1) 2ND REQUEST, NOTE THAT THIS SAME QUESTION BEING
 ASKED THE 2ND TIME UNDER THE BUILDING REVIEW SINCE THE
 OCCUPANT LOAD COUNT IS NOT FOUND ON THE ARCHITECTURAL
 PLANS. WHERE THE COMMON RESTROOMS ARE BEING DEMOLISHED
 AND REBUILT THE PLANS DO NOT HAVE A OCCUPANT LOAD COUNT
 PER FLOOR NOR DOES P0.1 SHOW COMPLIANCE WITH 2010
 FBC-PLUMBING TABLE 403.1.
  
 2) 2ND REQUEST, RESPONSE COMMENT INDICATES THE
 ACCESIBLE SHOWER DETAIL IS FOUND UNDER SHEET A0.06, NOT
 THERE EITHER. SHEET P2.2:
 2A) THE 2 SINGLE USER BATHROOMS (SHOWER) DO NOT SHOW
 DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE 608.2.1. 36"X36". TRANSFER TYPE
 SHOWER COMPARTMENTS.
  
 2B) THE 2 SINGLE USER BATHROOMS (SHOWER) DO NOT SHOW
 DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE
 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE
 PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS.
  
 2C) COMPLIED>
  
 2D) 2ND REQUEST, THE RESPONCE COMMENT INDICATES SEE
 SHEET P8.1 DETAIL # 11. NOTE THIS DETAIL SHOWS A GREASE
 INTERCEPTOR GT 2701-20 OR EQUAL. SUBMIT THE
 MANUFACTURERS SPECIFICATION SHEETS FOR REVIEW FOR CODE
 COMPLIANCE
 .
 USE OF THE WORD EQUAL SEE 2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH
 INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES
 SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE
 FOR SPECIFIC INFORMATION.
  
 THE OTHER ISSUE WITH THIS DETAIL SHOWS THE USE OF AIR
 ADMITTANCE VALVES. THE AIR ADMITTANCE VALVES CAN ONLY
 BE USED:
 917.3.1 LOCATION OF BRANCH.
 THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO THE
 DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK.
 917.3.2 RELIEF VENT.
 WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR
 BRANCH INTERVALS FROM THE TOP OF THE STACK, THE
 HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT
 THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, OR
 EXTEND OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE
 STACK AND THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED
 TO THE HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL
 BE SIZED IN ACCORDANCE WITH SECTION 916.2 AND INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL
 BE PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES.
  
 2E) COMPLIED.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]