| 2014-07-26 11:06:39 | PLUMBING PLAN REVIEW |
| | PERMIT: 14060196 |
| | ADD:777 S FLAGLER 12TH FLOOR |
| | CONT: WOOLEMS |
| | TEL: (561)835-0401 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SAT. JULY 26/2014 |
| | ACTION: DENIED |
| | |
| | 1) 2ND REQUEST, NOTE THAT THIS SAME QUESTION BEING |
| | ASKED THE 2ND TIME UNDER THE BUILDING REVIEW SINCE THE |
| | OCCUPANT LOAD COUNT IS NOT FOUND ON THE ARCHITECTURAL |
| | PLANS. WHERE THE COMMON RESTROOMS ARE BEING DEMOLISHED |
| | AND REBUILT THE PLANS DO NOT HAVE A OCCUPANT LOAD COUNT |
| | PER FLOOR NOR DOES P0.1 SHOW COMPLIANCE WITH 2010 |
| | FBC-PLUMBING TABLE 403.1. |
| | |
| | 2) 2ND REQUEST, RESPONSE COMMENT INDICATES THE |
| | ACCESIBLE SHOWER DETAIL IS FOUND UNDER SHEET A0.06, NOT |
| | THERE EITHER. SHEET P2.2: |
| | 2A) THE 2 SINGLE USER BATHROOMS (SHOWER) DO NOT SHOW |
| | DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH THE 2010 |
| | FBC-ACCESSIBILITY CODE 608.2.1. 36"X36". TRANSFER TYPE |
| | SHOWER COMPARTMENTS. |
| | |
| | 2B) THE 2 SINGLE USER BATHROOMS (SHOWER) DO NOT SHOW |
| | DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH THE 2010 |
| | FBC-ACCESSIBILITY CODE |
| | 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE |
| | PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS. |
| | |
| | 2C) COMPLIED> |
| | |
| | 2D) 2ND REQUEST, THE RESPONCE COMMENT INDICATES SEE |
| | SHEET P8.1 DETAIL # 11. NOTE THIS DETAIL SHOWS A GREASE |
| | INTERCEPTOR GT 2701-20 OR EQUAL. SUBMIT THE |
| | MANUFACTURERS SPECIFICATION SHEETS FOR REVIEW FOR CODE |
| | COMPLIANCE |
| | . |
| | USE OF THE WORD EQUAL SEE 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. |
| | |
| | THE OTHER ISSUE WITH THIS DETAIL SHOWS THE USE OF AIR |
| | ADMITTANCE VALVES. THE AIR ADMITTANCE VALVES CAN ONLY |
| | BE USED: |
| | 917.3.1 LOCATION OF BRANCH. |
| | THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO THE |
| | DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR |
| | BRANCH INTERVALS FROM THE TOP OF THE STACK. |
| | 917.3.2 RELIEF VENT. |
| | WHERE THE HORIZONTAL BRANCH IS LOCATED MORE THAN FOUR |
| | BRANCH INTERVALS FROM THE TOP OF THE STACK, THE |
| | HORIZONTAL BRANCH SHALL BE PROVIDED WITH A RELIEF VENT |
| | THAT SHALL CONNECT TO A VENT STACK OR STACK VENT, OR |
| | EXTEND OUTDOORS TO THE OPEN AIR. THE RELIEF VENT SHALL |
| | CONNECT TO THE HORIZONTAL BRANCH DRAIN BETWEEN THE |
| | STACK AND THE MOST DOWNSTREAM FIXTURE DRAIN CONNECTED |
| | TO THE HORIZONTAL BRANCH DRAIN. THE RELIEF VENT SHALL |
| | BE SIZED IN ACCORDANCE WITH SECTION 916.2 AND INSTALLED |
| | IN ACCORDANCE WITH SECTION 905. THE RELIEF VENT SHALL |
| | BE PERMITTED TO SERVE AS THE VENT FOR OTHER FIXTURES. |
| | |
| | 2E) COMPLIED. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |