2014-07-30 11:13:58777 SOUTH FLAGLER DRIVE
 PERMIT #14060196
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: THE ARCHITECTURAL RESPONSE TO PROTECT
 THE VERTICAL OPENING WITH SPRINKLERS IS TAKEN FROM
 CHAPTER 39 (EXISTING BUSINESS) SECTION 39.3.1.1(3). IF
 A MONUMENTAL STAIR WAS EXISTING, THIS WOULD BE
 PERMITTED TO REMAIN; HOWEVER, BECAUSE THIS IS A NEW
 STAIR INSTALLATION THE DESIGN NEEDS TO COMPLY WITH
 CHAPTER 38 (NEW BUSINESS) WHICH REFERENCES SECTION
 8.6.8.2. ALLOWING AN UNPROTECTED STAIR TO BE
 CONSTRUCTED WOULD CREATE A NONCONFORMITY THAT DID NOT
 PREVIOUSLY EXIST. MONUMENTAL STAIR COMMUNICATES
 DIRECTLY WITH CORRIDOR B, CORRIDOR C AND EXIT STAIR
 DOOR. I HAVE SERIOUS CONCERNS THAT SMOKE COULD AFFECT
 OCCUPANTS ABILITY TO EGRESS SAFELY.
  
 ORIGINAL COMMENT: SHEET A1.09: MONUMENTAL STAIR SHALL
 COMPLY WITH SECTION 8.6.8.2 (CONVENIENCE OPENINGS)
 WHEREBY THE FLOOR-TO-FLOOR OPENING IS REQUIRED TO BE
 SEPARATED FROM CORRIDORS AND EXIT ACCESS INTO EXISTING
 EXIT STAIR #1.
  
 RESPONSE COMMENT: DOORS TIED INTO THE FIRE ALARM SYSTEM
 ONLY COMPLIES WITH 1 OF 15 REQUIREMENTS LIST BELOW.
 ORIGINAL COMMENT: SHEET A1.21: ELEVATOR LOBBY DOORS ARE
 EQUIPPED WITH CARD READERS. PER SECTION 7.2.1.6.3, EACH
 ELEVATOR LANDING AND LOBBY SHALL HAVE ACCESS TO AT
 LEAST ON EXIT. EXIT ACCESS SHALL NOT REQUIRE THE USE OF
 A KEY, TOOL, SPECIAL KNOWLEDGE, OR SPECIAL EFFORT.
 DOORS SEPARATING THE ELEVATOR LOBBY FROM THE EXIT
 ACCESS SHALL BE PERMITTED TO BE ELECTRONICALLY LOCKED
 IN ACCORDANCE WITH SECTION 7.2.1.6.3 ELEVATOR LOBBY
 EXIT ACCESS DOOR ASSEMBLIES LOCKING: DOOR ASSEMBLIES
 SEPARATING THE ELEVATOR LOBBY FROM THE EXIT ACCESS
 SHALL BE PERMITTED TO BE ELECTRONICALLY LOCKED,
 PROVIDED THAT ALL THE FOLLOWING CRITERIA ARE MET:
 (1) THE ELECTRONIC SWITCH FOR RELEASING THE LOCK IS
 LISTED IN ACCORDANCE WITH UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS
 (2) THE BUILDING IS PROTECTED THROUGHOUT BY A FIRE
 ALARM SYSTEM
 (3) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 (4) WATERFLOW IN THE SPRINKLER SYSTEM REQUIRED BY
 7.2.1.6.3(3) IS ARRANGED TO INITIATE THE BUILDING FIRE
 ALARM SYSTEM.
 (5) THE ELEVATOR LOBBY IS PROTECTED BY AN APPROVED,
 SUPERVISED SMOKE DETECTION SYSTEM
 (6) DETECTION OF SMOKE BY THE DETECTION SYSTEM REQUIRED
 BY 7.2.1.6.3(5) IS ARRANGED TO INITIATE THE BUILDING
 FIRE ALARM SYSTEM.
 (7) INITIATION OF THE BUILDING FIRE ALARM SYSTEM BY
 OTHER THAN MANUAL FIRE ALARM BOXES UNLOCKS THE ELEVATOR
 LOBBY DOOR ASSEMBLY.
 (8) LOSS OF POWER TO THE ELEVATOR LOBBY ELECTRONIC LOCK
 SYSTEM UNLOCKS THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (9) THE ELEVATOR LOBBY ELECTRONIC LOCK SYSTEM IS NOT
 SUPPLIED WITH EMERGENCY OR STANDBY ELECTRICAL POWER.
 (10) ONCE UNLOCKED, THE ELEVATOR LOBBY DOOR ASSEMBLIES
 REMAIN UNLOCKED UNTIL THE BUILDING FIRE ALARM SYSTEM
 HAS BEEN MANUALLY RESET.
 (11) WHERE THE ELEVATOR LOBBY DOOR ASSEMBLIES REMAIN
 LATCHED AFTER BEING UNLOCKED, LATCH-RELEASING HARDWARE
 IS AFFIXED TO THE DOOR LEAVES.
 (12) A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED FOR
 COMMUNICATION BETWEEN THE ELEVATOR LOBBY AND A CENTRAL
 CONTROL POINT THAT IS CONSTANTLY STAFFED.
 (13) THE CENTRAL CONTROL POINT STAFF REQUIRED BY
 7.2.1.6.3(12) IS CAPABLE, TRAINED, AND AUTHORIZED TO
 PROVIDE EMERGENCY ASSISTANCE.
 (14) THE PROVISIONS OF DELAYED-EGRESS LOCKING SYSTEMS
 ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (15) THE PROVISIONS OF ACCESS-CONTROLLED EGRESS DOOR
 ASSEMBLIES ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR
 ASSEMBLIES.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730