2014-07-31 13:41:27DATE: 7/31/2014
 PROJECT: AMG PHILLIPS POINT EXPANSION
 PERMIT#: 14060196
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE THE LOCATION OF ELEVATOR MACHINE ROOM.
 INDICATE ALL CIRCUITRY AND DISCONNECT FOR MOTOR AND
 CONTROLS AND FIRE ALARM DEVICES REQUIRED IN THE
 ELEVATOR MACHINE ROOM FOR THE PERSONAL CEO ELEVATOR.
  
 2) CLEAR WORKING ACCESS REQUIRED FOR ELECTRICAL
 EQUIPMENT, FEEDING MECHANICAL EQUIPMENT.
  
 6) WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF SERVICE
 FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE AHJ
 SHALL BE NOTIFIED, AND THE BUILDING SHALL BE EVACUATED
 OR AN APPROVED FIRE WATCH SHALL BE PROVIDED FOR ALL
 PARTIES LEFT UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE
 ALARM SYSTEM HAS BEEN RETURNED TO SERVICE.
 [101:9.6.1.6] NFPA-1, CHAPTER 13 SECTION 13.7.1.4.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]