| Plan Review Notes For Permit 14060196 |
| Permit Number |
14060196 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-07-31 13:41:27 | DATE: 7/31/2014 | | | PROJECT: AMG PHILLIPS POINT EXPANSION | | | PERMIT#: 14060196 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 2ND ELECTRICAL PLAN REVIEW | | | ACTION: DENIED | | | | | | 1) INDICATE THE LOCATION OF ELEVATOR MACHINE ROOM. | | | INDICATE ALL CIRCUITRY AND DISCONNECT FOR MOTOR AND | | | CONTROLS AND FIRE ALARM DEVICES REQUIRED IN THE | | | ELEVATOR MACHINE ROOM FOR THE PERSONAL CEO ELEVATOR. | | | | | | 2) CLEAR WORKING ACCESS REQUIRED FOR ELECTRICAL | | | EQUIPMENT, FEEDING MECHANICAL EQUIPMENT. | | | | | | 6) WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF SERVICE | | | FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE AHJ | | | SHALL BE NOTIFIED, AND THE BUILDING SHALL BE EVACUATED | | | OR AN APPROVED FIRE WATCH SHALL BE PROVIDED FOR ALL | | | PARTIES LEFT UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE | | | ALARM SYSTEM HAS BEEN RETURNED TO SERVICE. | | | [101:9.6.1.6] NFPA-1, CHAPTER 13 SECTION 13.7.1.4.4 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|