| Date |
Text |
| 2014-07-26 11:09:08 | BUILDING PLAN REVIEW |
| | PERMIT: 14060196 |
| | ADD:777 S FLAGLER 12TH FLOOR |
| | CONT: WOOLEMS |
| | TEL: (561)835-0401 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: SAT. JULY 26/2014 |
| | ACTION: DENIED |
| | |
| | 1-2) COMPLIED. |
| | |
| | 3)2ND REQUEST. SHEET A0.08 LIFE SAFETY PLANS:MISSING |
| | PLAN REVIEW CRITERIA: |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS OR NET TABLE FBC-B 1004.1.1. PER FLOOR |
| | |
| | 4) THE STRUCTURAL WORK ON THIS BUILDING ISCLASSIFYING |
| | IT AS A :THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 4A) COMPLIED. |
| | |
| | 4B) THRESHOLD INSPECTOR: |
| | WPB AMENDMENT 109.3.6.2 W.P.B. CONSTRUCTION SERVICES |
| | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL |
| | INSPECTOR AS REQUIRED BY FL S S 553.79(5) FLORIDA |
| | STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS |
| | CODE. A THRESHOLD AGREEMENT WILL NEED TO BE SIGNED BY |
| | ALL PARTIES, PLEASE PROVIDE A E-MAIL ADDRESS THAT WE |
| | CAN SEND ALL THE REQUIRED DOCUMENTS. |
| | |
| | 4C) COMPLIED. |
| | |
| | |
| | 4D) CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 OR [email protected] FOR FURTHER |
| | INFORMATION: |
| | |
| | 4D) (1) COMPLIED. THE CONTRACTOR WILL PRODUCE A JOB |
| | SUMMARY OR HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 4D) (2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A |
| | RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| | THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 5) COMPLIED. |
| | |
| | 6) SHEET 015 A1.10 LEVEL 15: |
| | |
| | 6A) DOOR # 1502 APPEARS TO HAVE ONLY 16 1/2 INCHES ON |
| | THE LATCH SIDE OF THE DOOR, SEE 2010 FL ACC CODE FIGURE |
| | 404.2.4.1. (A). |
| | |
| | 6B) COMPLIED. |
| | |
| | 6C) COMPLIED. |
| | |
| | 7) 2ND REQUEST ,RESPONSE INDICATES DETAILS FOR FIRE |
| | RESISTANCE IS FOUND ON SHEET A0.04. THERE ARE NO |
| | DETAILS SHOWING CODE COMPLIANCE. |
| | STRUCTURAL SHEETS SHOW STEEL FRAMING MEMBERS, THIS IS A |
| | TYPE 1A BUILDING SHOW COMPLIANCE WITH TABLE 603 WITH |
| | REQUIRED FIRE RESISTANCE RATING REQUIREMENTS FOR |
| | BUILDING ELEMENTS (HOURS) PROVIDE THICKENESS AND HOUR |
| | RATING. |
| | |
| | 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | NOTE THERE ARE ALOT OF THE REQUIRED DOCUMENTS PRODUCT |
| | APPROVALS AND MANUFACTURERS SPECIFICATIONS THAT WERE |
| | LOADED INTO THE RESPONSE FOLDER RATHER THAN A SEPARATE |
| | DOCUMENT FOLDER. I'LL BE CHECKING IF OUR LIBRIAN WILL |
| | BE ABLE TO TRANSFER THESE ITEMS INTO THE CORRECT |
| | FOLDER. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |