| 2014-07-07 16:30:50 | PLUMBING PLAN REVIEW |
| | PERMIT: 14060196 |
| | ADD:777 S FLAGLER 12TH FLOOR |
| | CONT: WOOLEMS |
| | TEL: (561)835-0401 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. JULY 07/2014 |
| | ACTION: DENIED |
| | |
| | 1) WHERE THE COMMON RESTROOMS ARE BEING DEMOLISHED AND |
| | REBUILT THE PLANS DO NOT HAVE A OCCUPANT LOAD COUNT PER |
| | FLOOR NOR DOES P0.1 SHOW COMPLIANCE WITH 2010 |
| | FBC-PLUMBING TABLE 403.1. |
| | |
| | 2) SHEET P2.2: |
| | 2A) THE 2 SINGLE USER BATHROOMS (SHOWER) DO NOT SHOW |
| | DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH THE 2010 |
| | FBC-ACCESSIBILITY CODE 608.2.1. 36"X36". TRANSFER TYPE |
| | SHOWER COMPARTMENTS. |
| | |
| | 2B) THE 2 SINGLE USER BATHROOMS (SHOWER) DO NOT SHOW |
| | DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH THE 2010 |
| | FBC-ACCESSIBILITY CODE |
| | 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE |
| | PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS. |
| | |
| | 2C) THE 2 SINGLE USER BATHROOMS (SHOWERS) ON THIS SHEET |
| | AND P5.1 THE SANITARY ISOMETRIC ARE DRAWN AS A |
| | HORIZONTAL WET WENT. HORIZONTAL WET VENTS ARE TO BE |
| | USED ONLY IN SINGLE FAMILY RESIDENCE 909.1 AND |
| | COMMENTARY & BOAF 2007 INFORMAL INTERPRETATION 6090. |
| | THE OTHER ISSUE WITH THE SHOWER FIXTURE ARM IT EXCEEDS |
| | THE ALLOWABLE DISTANCE FROM FIXTURE TRAP TO VENT TABLE |
| | 906.1. |
| | |
| | 2D) THE REMODELING OF THE KITCHEN AND SANITARY DRAINAGE |
| | THERE IS A COMMERCIAL KITCHEN 3 COMPARTMENT SINK AND NO |
| | GREASE INTERCEPTOR. |
| | FBC-P 1003.1 WHERE REQUIRED. INTERCEPTORS AND |
| | SEPARATORS SHALL BE PROVIDED TO PREVENT THE DISCHARGE |
| | OF OIL, GREASE, SAND AND OTHER SUBSTANCES HARMFUL OR |
| | HAZARDOUS TO THE BUILDING DRAINAGE SYSTEM, THE PUBLIC |
| | SEWER, |
| | 003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE |
| | REMOVAL DEVICES REQUIRED. |
| | A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE |
| | SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES |
| | AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD |
| | PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL |
| | KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY |
| | CAFETERIAS AND CLUBS. |
| | |
| | 2E) PLEASE INDICATE THE EXISTANCE OF A SERVICE SINK |
| | INCOMPLIANCE WITH FBC-P TABLE 403.1. |
| | |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |