2014-07-07 16:30:50PLUMBING PLAN REVIEW
 PERMIT: 14060196
 ADD:777 S FLAGLER 12TH FLOOR
 CONT: WOOLEMS
 TEL: (561)835-0401
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. JULY 07/2014
 ACTION: DENIED
  
 1) WHERE THE COMMON RESTROOMS ARE BEING DEMOLISHED AND
 REBUILT THE PLANS DO NOT HAVE A OCCUPANT LOAD COUNT PER
 FLOOR NOR DOES P0.1 SHOW COMPLIANCE WITH 2010
 FBC-PLUMBING TABLE 403.1.
  
 2) SHEET P2.2:
 2A) THE 2 SINGLE USER BATHROOMS (SHOWER) DO NOT SHOW
 DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE 608.2.1. 36"X36". TRANSFER TYPE
 SHOWER COMPARTMENTS.
  
 2B) THE 2 SINGLE USER BATHROOMS (SHOWER) DO NOT SHOW
 DIMENSIONS FOR SHOWERS AND COMPLIANCE WITH THE 2010
 FBC-ACCESSIBILITY CODE
 608.4 SEATS. A FOLDING OR NON-FOLDING SEAT SHALL BE
 PROVIDED IN TRANSFER TYPE SHOWER COMPARTMENTS.
  
 2C) THE 2 SINGLE USER BATHROOMS (SHOWERS) ON THIS SHEET
 AND P5.1 THE SANITARY ISOMETRIC ARE DRAWN AS A
 HORIZONTAL WET WENT. HORIZONTAL WET VENTS ARE TO BE
 USED ONLY IN SINGLE FAMILY RESIDENCE 909.1 AND
 COMMENTARY & BOAF 2007 INFORMAL INTERPRETATION 6090.
 THE OTHER ISSUE WITH THE SHOWER FIXTURE ARM IT EXCEEDS
 THE ALLOWABLE DISTANCE FROM FIXTURE TRAP TO VENT TABLE
 906.1.
  
 2D) THE REMODELING OF THE KITCHEN AND SANITARY DRAINAGE
 THERE IS A COMMERCIAL KITCHEN 3 COMPARTMENT SINK AND NO
 GREASE INTERCEPTOR.
 FBC-P 1003.1 WHERE REQUIRED. INTERCEPTORS AND
 SEPARATORS SHALL BE PROVIDED TO PREVENT THE DISCHARGE
 OF OIL, GREASE, SAND AND OTHER SUBSTANCES HARMFUL OR
 HAZARDOUS TO THE BUILDING DRAINAGE SYSTEM, THE PUBLIC
 SEWER,
 003.3.1 GREASE INTERCEPTORS AND AUTOMATIC GREASE
 REMOVAL DEVICES REQUIRED.
 A GREASE INTERCEPTOR OR AUTOMATIC GREASE REMOVAL DEVICE
 SHALL BE REQUIRED TO RECEIVE THE DRAINAGE FROM FIXTURES
 AND EQUIPMENT WITH GREASE-LADEN WASTE LOCATED IN FOOD
 PREPARATION AREAS, SUCH AS IN RESTAURANTS, HOTEL
 KITCHENS, HOSPITALS, SCHOOL KITCHENS, BARS, FACTORY
 CAFETERIAS AND CLUBS.
  
 2E) PLEASE INDICATE THE EXISTANCE OF A SERVICE SINK
 INCOMPLIANCE WITH FBC-P TABLE 403.1.
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]