| Plan Review Notes For Permit 14060196 |
| Permit Number |
14060196 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-14 15:54:32 | PLAN DENIED | | | 1) SEPARATE APPLICATION, PLAN AND PERMIT REQUIRED FOR | | | HOOD | | | AND GREASE DUCT. 107 FBC 2010 | | | 2) PAGE M3.0 12TH. FLOOR MISSING DUCT SIZE. 107 FBC | | | 2010 | | | 3) PAGE M3.2 14TH FL. TWO SEPARATE VAV BOXES SERVING | | | ONE GRILL | | | IN TWO OR MORE LOCATIONS, SIZE RETURN AIR DUCT FROM VAV | | | BOXES | | | 4) PAGE M3.3 SAME AS M3.2 | | | 5) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROL | | | 2010 FLORIDA ENERGY CODE | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX-561-805-6676 |
|