Plan Review Notes
Plan Review Notes For Permit 14060196
Permit Number 14060196
Review Stop M
Sequence Number 1
Notes
Date Text
2014-07-14 15:54:32PLAN DENIED
 1) SEPARATE APPLICATION, PLAN AND PERMIT REQUIRED FOR
 HOOD
 AND GREASE DUCT. 107 FBC 2010
 2) PAGE M3.0 12TH. FLOOR MISSING DUCT SIZE. 107 FBC
 2010
 3) PAGE M3.2 14TH FL. TWO SEPARATE VAV BOXES SERVING
 ONE GRILL
 IN TWO OR MORE LOCATIONS, SIZE RETURN AIR DUCT FROM VAV
 BOXES
 4) PAGE M3.3 SAME AS M3.2
 5) REFER TO SECTION 503.2.4.4 SHUT OFF DAMPER CONTROL
 2010 FLORIDA ENERGY CODE
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX-561-805-6676