Plan Review Notes
Plan Review Notes For Permit 14060196
Permit Number 14060196
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2014-06-27 16:31:17777 SOUTH FLAGLER DRIVE
 PERMIT #14060196
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 SHEET A1.09: MONUMENTAL STAIR SHALL COMPLY WITH SECTION
 8.6.8.2 (CONVENIENCE OPENINGS) WHEREBY THE
 FLOOR-TO-FLOOR OPENING IS REQUIRED TO BE SEPARATED FROM
 CORRIDORS AND EXIT ACCESS INTO EXISTING EXIT STAIR #1.
  
 SHEET A1.21: ELEVATOR LOBBY DOORS ARE EQUIPPED WITH
 CARD READERS. PER SECTION 7.2.1.6.3, EACH ELEVATOR
 LANDING AND LOBBY SHALL HAVE ACCESS TO AT LEAST ON
 EXIT. EXIT ACCESS SHALL NOT REQUIRE THE USE OF A KEY,
 TOOL, SPECIAL KNOWLEDGE, OR SPECIAL EFFORT. DOORS
 SEPARATING THE ELEVATOR LOBBY FROM THE EXIT ACCESS
 SHALL BE PERMITTED TO BE ELECTRONICALLY LOCKED IN
 ACCORDANCE WITH SECTION 7.2.1.6.3 ELEVATOR LOBBY EXIT
 ACCESS DOOR ASSEMBLIES LOCKING: DOOR ASSEMBLIES
 SEPARATING THE ELEVATOR LOBBY FROM THE EXIT ACCESS
 SHALL BE PERMITTED TO BE ELECTRONICALLY LOCKED,
 PROVIDED THAT ALL THE FOLLOWING CRITERIA ARE MET:
 (1) THE ELECTRONIC SWITCH FOR RELEASING THE LOCK IS
 LISTED IN ACCORDANCE WITH UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS
 (2) THE BUILDING IS PROTECTED THROUGHOUT BY A FIRE
 ALARM SYSTEM
 (3) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 (4) WATERFLOW IN THE SPRINKLER SYSTEM REQUIRED BY
 7.2.1.6.3(3) IS ARRANGED TO INITIATE THE BUILDING FIRE
 ALARM SYSTEM.
 (5) THE ELEVATOR LOBBY IS PROTECTED BY AN APPROVED,
 SUPERVISED SMOKE DETECTION SYSTEM
 (6) DETECTION OF SMOKE BY THE DETECTION SYSTEM REQUIRED
 BY 7.2.1.6.3(5) IS ARRANGED TO INITIATE THE BUILDING
 FIRE ALARM SYSTEM.
 (7) INITIATION OF THE BUILDING FIRE ALARM SYSTEM BY
 OTHER THAN MANUAL FIRE ALARM BOXES UNLOCKS THE ELEVATOR
 LOBBY DOOR ASSEMBLY.
 (8) LOSS OF POWER TO THE ELEVATOR LOBBY ELECTRONIC LOCK
 SYSTEM UNLOCKS THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (9) THE ELEVATOR LOBBY ELECTRONIC LOCK SYSTEM IS NOT
 SUPPLIED WITH EMERGENCY OR STANDBY ELECTRICAL POWER.
 (10) ONCE UNLOCKED, THE ELEVATOR LOBBY DOOR ASSEMBLIES
 REMAIN UNLOCKED UNTIL THE BUILDING FIRE ALARM SYSTEM
 HAS BEEN MANUALLY RESET.
 (11) WHERE THE ELEVATOR LOBBY DOOR ASSEMBLIES REMAIN
 LATCHED AFTER BEING UNLOCKED, LATCH-RELEASING HARDWARE
 IS AFFIXED TO THE DOOR LEAVES.
 (12) A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED FOR
 COMMUNICATION BETWEEN THE ELEVATOR LOBBY AND A CENTRAL
 CONTROL POINT THAT IS CONSTANTLY STAFFED.
 (13) THE CENTRAL CONTROL POINT STAFF REQUIRED BY
 7.2.1.6.3(12) IS CAPABLE, TRAINED, AND AUTHORIZED TO
 PROVIDE EMERGENCY ASSISTANCE.
 (14) THE PROVISIONS OF DELAYED-EGRESS LOCKING SYSTEMS
 ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (15) THE PROVISIONS OF ACCESS-CONTROLLED EGRESS DOOR
 ASSEMBLIES ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR
 ASSEMBLIES.
  
 SHEET A6.01: PLAN INDICATES WOOD VENEER TO BE APPLIED
 TO EXISTING STAIR DOORS. EXISTING FIRE RATED STAIR
 DOORS ARE NOT PERMITTED TO BE ALTERED UNLESS
 SPECIFICALLY LISTED.
  
 FS1.1: PROVIDE ORDINARY HAZARD SPRINKLER DENSITIES FOR
 12TH FLOOR STORAGE ROOM AND 14TH FLOOR STORAGE #1418.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  