| Date |
Text |
| 2014-06-27 16:31:17 | 777 SOUTH FLAGLER DRIVE |
| | PERMIT #14060196 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | NO ADDRESS PROVIDED IN THE PLAN TITLEBLOCK INFORMATION. |
| | |
| | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND |
| | DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| | NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| | REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| | PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| | OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| | RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| | |
| | PROVIDE DRAWING NOTE INDICATING, "FIRE PROTECTION |
| | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND |
| | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION |
| | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A |
| | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A |
| | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED |
| | BY EMAIL ([email protected]) OR IN WRITING (FAX: |
| | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE |
| | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY." |
| | |
| | SHEET A1.09: MONUMENTAL STAIR SHALL COMPLY WITH SECTION |
| | 8.6.8.2 (CONVENIENCE OPENINGS) WHEREBY THE |
| | FLOOR-TO-FLOOR OPENING IS REQUIRED TO BE SEPARATED FROM |
| | CORRIDORS AND EXIT ACCESS INTO EXISTING EXIT STAIR #1. |
| | |
| | SHEET A1.21: ELEVATOR LOBBY DOORS ARE EQUIPPED WITH |
| | CARD READERS. PER SECTION 7.2.1.6.3, EACH ELEVATOR |
| | LANDING AND LOBBY SHALL HAVE ACCESS TO AT LEAST ON |
| | EXIT. EXIT ACCESS SHALL NOT REQUIRE THE USE OF A KEY, |
| | TOOL, SPECIAL KNOWLEDGE, OR SPECIAL EFFORT. DOORS |
| | SEPARATING THE ELEVATOR LOBBY FROM THE EXIT ACCESS |
| | SHALL BE PERMITTED TO BE ELECTRONICALLY LOCKED IN |
| | ACCORDANCE WITH SECTION 7.2.1.6.3 ELEVATOR LOBBY EXIT |
| | ACCESS DOOR ASSEMBLIES LOCKING: DOOR ASSEMBLIES |
| | SEPARATING THE ELEVATOR LOBBY FROM THE EXIT ACCESS |
| | SHALL BE PERMITTED TO BE ELECTRONICALLY LOCKED, |
| | PROVIDED THAT ALL THE FOLLOWING CRITERIA ARE MET: |
| | (1) THE ELECTRONIC SWITCH FOR RELEASING THE LOCK IS |
| | LISTED IN ACCORDANCE WITH UL 294, STANDARD FOR ACCESS |
| | CONTROL SYSTEM UNITS |
| | (2) THE BUILDING IS PROTECTED THROUGHOUT BY A FIRE |
| | ALARM SYSTEM |
| | (3) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| | (4) WATERFLOW IN THE SPRINKLER SYSTEM REQUIRED BY |
| | 7.2.1.6.3(3) IS ARRANGED TO INITIATE THE BUILDING FIRE |
| | ALARM SYSTEM. |
| | (5) THE ELEVATOR LOBBY IS PROTECTED BY AN APPROVED, |
| | SUPERVISED SMOKE DETECTION SYSTEM |
| | (6) DETECTION OF SMOKE BY THE DETECTION SYSTEM REQUIRED |
| | BY 7.2.1.6.3(5) IS ARRANGED TO INITIATE THE BUILDING |
| | FIRE ALARM SYSTEM. |
| | (7) INITIATION OF THE BUILDING FIRE ALARM SYSTEM BY |
| | OTHER THAN MANUAL FIRE ALARM BOXES UNLOCKS THE ELEVATOR |
| | LOBBY DOOR ASSEMBLY. |
| | (8) LOSS OF POWER TO THE ELEVATOR LOBBY ELECTRONIC LOCK |
| | SYSTEM UNLOCKS THE ELEVATOR LOBBY DOOR ASSEMBLIES. |
| | (9) THE ELEVATOR LOBBY ELECTRONIC LOCK SYSTEM IS NOT |
| | SUPPLIED WITH EMERGENCY OR STANDBY ELECTRICAL POWER. |
| | (10) ONCE UNLOCKED, THE ELEVATOR LOBBY DOOR ASSEMBLIES |
| | REMAIN UNLOCKED UNTIL THE BUILDING FIRE ALARM SYSTEM |
| | HAS BEEN MANUALLY RESET. |
| | (11) WHERE THE ELEVATOR LOBBY DOOR ASSEMBLIES REMAIN |
| | LATCHED AFTER BEING UNLOCKED, LATCH-RELEASING HARDWARE |
| | IS AFFIXED TO THE DOOR LEAVES. |
| | (12) A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED FOR |
| | COMMUNICATION BETWEEN THE ELEVATOR LOBBY AND A CENTRAL |
| | CONTROL POINT THAT IS CONSTANTLY STAFFED. |
| | (13) THE CENTRAL CONTROL POINT STAFF REQUIRED BY |
| | 7.2.1.6.3(12) IS CAPABLE, TRAINED, AND AUTHORIZED TO |
| | PROVIDE EMERGENCY ASSISTANCE. |
| | (14) THE PROVISIONS OF DELAYED-EGRESS LOCKING SYSTEMS |
| | ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR ASSEMBLIES. |
| | (15) THE PROVISIONS OF ACCESS-CONTROLLED EGRESS DOOR |
| | ASSEMBLIES ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR |
| | ASSEMBLIES. |
| | |
| | SHEET A6.01: PLAN INDICATES WOOD VENEER TO BE APPLIED |
| | TO EXISTING STAIR DOORS. EXISTING FIRE RATED STAIR |
| | DOORS ARE NOT PERMITTED TO BE ALTERED UNLESS |
| | SPECIFICALLY LISTED. |
| | |
| | FS1.1: PROVIDE ORDINARY HAZARD SPRINKLER DENSITIES FOR |
| | 12TH FLOOR STORAGE ROOM AND 14TH FLOOR STORAGE #1418. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |