2014-07-10 15:03:04DATE: 7/9/2014
 PROJECT: AMG PHILLIPS POINT EXPANSION
 PERMIT#: 14060196
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) BOXES, CONDUIT BODIES, AND HANDHOLE ENCLOSURES SHALL
 BE INSTALLED SO THAT THE WIRING CONTAINED IN THEM CAN
 BE RENDERED ACCESSIBLE WITHOUT REMOVING ANY PART OF THE
 BUILDING OR, IN UNDERGROUND CIRCUITS, WITHOUT
 EXCAVATING SIDEWALKS, PAVING, EARTH, OR OTHER SUBSTANCE
 THAT IS TO BE USED TO ESTABLISH THE FINISHED GRADE. NEC
 314.29. THE POWER PACKS FOR MOTION SENSORS APPEAR TO BE
 LOCATED IN AREAS WITH DRYWALL CEILINGS. ALL
 TRANSFORMERS, LED DRIVERS JUNCTION BOXES, POWER PACK
 AND THE LIKE SHALL BE INSTALLED SO AS TO REMAIN
 ACCESSIBLE AFTER INSTALLATION AND CONSTRUCTION IS
 COMPLETE.
  
 2) PROVIDE PRODUCT APPROVALS FOR ALL FIXTURES. LISTING
 AND LABELING REQUIRED BY AN APPROVED TESTING LAB. IN
 JUDGING EQUIPMENT, CONSIDERATION SUCH AS THE FOLLOWING
 SHALL BE EVALUATED: SUITABILITY FOR INSTALLATION AND
 USE IN CONFORMITY WITH THE PROVISIONS OF THIS CODE. NEC
 110.3(A)(1 THRU 8)
  
 3) PROVIDE PRODUCT APPROVALS AND CUT SHEETS FOR FLOOR
 BOXES TO SHOW CODE COMPLIANCE WITH FIRE RATING FROM
 FLOOR TO FLOOR. ADDITIONAL INFORMATION REQUIRED. FBC
 107.2.1.3
  
 4) IDENTIFY ALL NEW FEEDERS ON THE RISER DIAGRAM.
 ADDITIONAL INFORMATION REQUIRED. FBC 107.2.1.3
  
 5) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE 210.8(A)(3), ALL 15
 AND 20AMP, 125V AND 250V RECEPTACLES INSTALLED IN IN A
 WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS
 WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS
 INSERTED. ALL 15- AND 20-AMPERE, 125- AND 250-VOLT
 NON-LOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE. NEC 406.8(B)(1)
  
 6) WHERE A REQUIRED FIRE ALARM SYSTEM IS OUT OF SERVICE
 FOR MORE THAN 4 HOURS IN A 24-HOUR PERIOD, THE AHJ
 SHALL BE NOTIFIED, AND THE BUILDING SHALL BE EVACUATED
 OR AN APPROVED FIRE WATCH SHALL BE PROVIDED FOR ALL
 PARTIES LEFT UNPROTECTED BY THE SHUTDOWN UNTIL THE FIRE
 ALARM SYSTEM HAS BEEN RETURNED TO SERVICE.
 [101:9.6.1.6] NFPA-1, CHAPTER 13 SECTION 13.7.1.4.4
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  