2014-06-15 13:13:25BUILDING PLAN REVIEW
 REVISION: 14060174
 PERMIT: 130906958
 ADD: 1865 PALM BEACH LAKES SHELL BUILDING C
 CONT: EMJ
 TEL: (561)348-4805
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SUN. JUNE 15/ 2014
 ACTION: DENIED
  
 1) THE REVISION # D DEPICTS WHAT APPEARS TO BE FIRE
 WALLS SEPARATING BUILDING C & B2 INTO SEPARATE
 BUILDINGS.SHEET A121. UNDER THE 2010 FBC-B 507.3 ONE
 STORY MERCANTILE OCCUPANCIES HAVE UNLIMITED AREA WHEN
 FIRE SPRINKLERED. PLEASE PROVIDE A NARATIVE TO EXPLAIN
 WHAT REVISION # D CONSIST OF. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. REVISION # D AT THE FRONT OF
 THE BUILDING, NDICATES ALSO A 1 HOUR WALL IS BEING
 BUILT BACK AWAY FORM THE 3 HR RATED WALL BUT THE PLANS
 DO NOT INDICATE ANY WALLS BEING BUILT THERE?
  