| Plan Review Notes For Permit 14060154 |
| Permit Number |
14060154 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-05 11:33:38 | ADDRESS: 2400 N. FLAGLER DR WPB | | | PERMIT#:14060154 | | | 1ST ELECTRICAL REVIEW | | | ACTION: DENIED. | | | CODE: 2008 NEC AND 2010 FBC | | | | | | DEFICIENCIES: | | | | | | 1) PROVIDE VOLTAGE DROP CALCULATION ON PLANS PER FBC | | | 107.2.1. | | | 2) PROVIDE ENGINEERING TO INDICATE COMPLIANCE WITH FBC | | | WIND LOAD REQUIREMENTS AND INSTALLATION DETAILS. PER | | | FBC AND NOTE ON SHEET E-2. | | | 3) ALTER DETAIL ON SHEET E-2 TO INDICATE ABOVE GRADE | | | CONDUIT TO BE SCHEDULE 80 PER THE SPECIFICATION NOTE 20 | | | ON THE SAME SHEET. | | | 4) INDICATE BURIAL DEPTH ON PLANS PER, NEC 300.5 | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. | | | 561-805-6717 OR [email protected] | | | |
|