| 2014-07-29 09:51:35 | DATE: 6/21/2014 |
| | PROJECT: L.A VINAS M.D |
| | PERMIT#: 14060133 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | NOTE: THE RE-SUBMITTAL IS NOT OF SUFFICIENT SIZE AND |
| | CLARITY TO SHOW APPROPRIATE DETAIL. CONSTRUCTION |
| | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE |
| | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED |
| | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. FBC 107.2.1 |
| | |
| | ADDITIONALLY, REQUEST THE DENIED PACKAGE WHEN YOU |
| | ARRIVE TO RE-SUBMIT. REPLACE THE CORRECTED PAGES INTO |
| | THE SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARETIVE REVIEW. . |
| | |
| | PLEASE INCLUDE ALL THE FOLLOWING DUPLICATE COMMENTS IN |
| | THE RESUBMITTAL: |
| | |
| | 1) INDICATE ALL PATIENT CARE AREAS SHALL BE IN |
| | COMPLIANCE WITH ARTICALE 517 OF THE NEC. SEE BELOW: |
| | WIRING IN PATIENT CARE AREAS SHALL COMPLY WITH |
| | 517.13(A) AND (B). NEC 517.13 |
| | (A) ALL BRANCH CIRCUITS SERVING PATIENT CARE AREAS |
| | SHALL BE PROVIDED WITH AN EFFECTIVE GROUND FAULT |
| | CURRENT PATH BY INSTALLATION IN A METAL RACEWAY SYSTEM |
| | OR A CABLE HAVING A METALLIC ARMOR SHEATH ASSEMBLY. THE |
| | METAL RACEWAY SYSTEM OR METALLIC CABLE ARMOR OR SHEATH |
| | ASSEMBLY SHALL ITSELF QUALIFY AS AN EQUIPMENT GROUNDING |
| | CONDUCTOR IN ACCORDANCE WITH 250.118. |
| | (B) THE GROUNDING TERMINALS OF ALL RECEPTACLES AND |
| | NON-CURRENT-CARRYING CONDUCTIVE SURFACES FIXED |
| | ELECTRICAL EQUIPMENT LIKELY TO BECOME ENERGIZED THAT |
| | ARE SUBJECT TO PERSONAL CONTACT OPERATING AT OVER 100 |
| | VOLTS SHALL BE CONNECTED TO AN INSULATED COPPER |
| | EQUIPMENT GROUNDING CONDUCTOR. THE EQUIPMENT GROUNDING |
| | CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE |
| | 250.122 AND INSTALLED IN METAL RACEWAYS OR AS A PART OF |
| | LISTED CABLES HAVING A METALLIC ARMOR OR SHEATH |
| | ASSEMBLY WITH THE BRANCH CIRCUIT CONDUCTORS SUPPLYING |
| | THESE RECEPTACLES OR FIXED EQUIPMENT. |
| | |
| | 2) RISER DIAGRAM ON SHEET E-1.0 INDICATES A 200AMP MAIN |
| | DISCONNECT FEEDING A 200AMP MCB PANEL WITH 3, #1CU IN |
| | 1,1/2" CONDUIT PRESUMED TO BE EXISTING AND UNDERGROUND. |
| | #1CU THHN IS NOT ADEQUATE TO CONNECT TO A 200AMP OCPD. |
| | **# 6 CU IS NOT THE ADAQUATE SIZE TO USE FOR A GEC WHEN |
| | USING 3/0 CU SERVICE ENTRANCE CONDUCTORS.** PLEASE |
| | REVISE THE RISER TO THE APPROPRIATE SIZE CONDUCTOR AND |
| | RACEWAY TO SUPPORT THE LOAD. **RESIZE ALL THE CONDUITS |
| | AND CONDUCTORS ON THE LINE SIDE AND ON THE LOAD SIDE |
| | FEEDING THE PANEL.INCLUDING THE GROUNDING ELECTRODE |
| | CONDUCTOR AND THE EQUIPMENT GROUND CONDUCTORS.* |
| | |
| | 3) PROVIDE A SAFETY LABELING SCHEDULE FOR ARC FLASH |
| | PROTECTION AND FOR THE PANEL BOARDS AND MAIN |
| | DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22 |
| | |
| | 4) PLEASE INDICATE COMPLIANCE WITH FBC-ENERGY. |
| | ELECTRICAL POWER AND LIGHTING SYSTEMS. (MANDATORY) |
| | SECTION 505 |
| | A) INTERIOR LIGHTING CONTROLS. EACH AREA ENCLOSED BY |
| | WALLS OR FLOOR-TO-CEILING PARTITIONS SHALL HAVE AT |
| | LEAST ONE CONTROL DEVICE TO INDEPENDENTLY CONTROL THE |
| | GENERAL LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE |
| | SHALL BE READILY ACCESSIBLE AND LOCATED SO THE |
| | OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. 505.2.1 |
| | B) BUILDINGS LARGER THAN 5000SQ.FT. SHALL BE EQUIPPED |
| | WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING |
| | IN THOSE AREAS. THIS AUTOMATIC CONTROL DEVICE SHALL |
| | FUNCTION ON EITHER; |
| | 1) A SCHEDULED BASIS, USING TIME OF DAY, WITH AN |
| | INDEPENDENT PROGRAM SCHEDULE THAT CONTROLS THE INTERIOR |
| | LIGHTING IN THE AREAS THAT DO NOT EXCEED 25000SQFT AND |
| | ARE NOT MORE THAN ONE FLOOR; OR |
| | 2) AN OCCUPANT SENSOR THAT SHALL TURN LIGHTING OFF |
| | WITHIN 30 MINUTES OF AN OCCUPANT LEAVING A SPACE; OR |
| | 3) A SIGNAL FROM ANOTHER CONTROL OR ALARM SYSTEM THAT |
| | INDICATES THE AREA IS UNOCCUPIED. 505.2.2, |
| | C) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN |
| | SHOWING COMPLIANCE WITH THE FBC ENERGY 505.5.3 |
| | |
| | SEPARATE PERMITS WITH SHOP DRAWINGS REQUIRED FOR FIRE |
| | ALARM, SECURITY, CCTV, AUDIO/VIDEO, NETWORK, AND SIGNS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER. 561-805-6717, |
| | [email protected]. |