| 2014-06-23 07:25:18 | DATE: 6/21/2014 |
| | PROJECT: |
| | PERMIT#: |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) INDICATE ALL PATIENT CARE AREAS SHALL BE IN |
| | COMPLIANCE WITH ARTICALE 517 OF THE NEC. SEE BELOW: |
| | WIRING IN PATIENT CARE AREAS SHALL COMPLY WITH |
| | 517.13(A) AND (B). NEC 517.13 |
| | (A) ALL BRANCH CIRCUITS SERVING PATIENT CARE AREAS |
| | SHALL BE PROVIDED WITH AN EFFECTIVE GROUND FAULT |
| | CURRENT PATH BY INSTALLATION IN A METAL RACEWAY SYSTEM |
| | OR A CABLE HAVING A METALLIC ARMOR SHEATH ASSEMBLY. THE |
| | METAL RACEWAY SYSTEM OR METALLIC CABLE ARMOR OR SHEATH |
| | ASSEMBLY SHALL ITSELF QUALIFY AS AN EQUIPMENT GROUNDING |
| | CONDUCTOR IN ACCORDANCE WITH 250.118. |
| | (B) THE GROUNDING TERMINALS OF ALL RECEPTACLES AND |
| | NON-CURRENT-CARRYING CONDUCTIVE SURFACES FIXED |
| | ELECTRICAL EQUIPMENT LIKELY TO BECOME ENERGIZED THAT |
| | ARE SUBJECT TO PERSONAL CONTACT OPERATING AT OVER 100 |
| | VOLTS SHALL BE CONNECTED TO AN INSULATED COPPER |
| | EQUIPMENT GROUNDING CONDUCTOR. THE EQUIPMENT GROUNDING |
| | CONDUCTOR SHALL BE SIZED IN ACCORDANCE WITH TABLE |
| | 250.122 AND INSTALLED IN METAL RACEWAYS OR AS A PART OF |
| | LISTED CABLES HAVING A METALLIC ARMOR OR SHEATH |
| | ASSEMBLY WITH THE BRANCH CIRCUIT CONDUCTORS SUPPLYING |
| | THESE RECEPTACLES OR FIXED EQUIPMENT. |
| | |
| | 2) RISER DIAGRAM ON SHEET E-1.0 INDICATES A 200AMP MAIN |
| | DISCONNECT FEEDING A 200AMP MCB PANEL WITH 3, #1CU IN |
| | 1,1/2" CONDUIT PRESUMED TO BE EXISTING AND UNDERGROUND. |
| | #1CU THHN IS NOT ADEQUATE TO CONNECT TO A 200AMP OCPD. |
| | PLEASE REVISE THE RISER TO THE APPROPRIATE SIZE |
| | CONDUCTOR AND RACEWAY TO SUPPORT THE LOAD. |
| | |
| | 3) PROVIDE A SAFETY LABELING SCHEDULE FOR ARC FLASH |
| | PROTECTION AND FOR THE PANEL BOARDS AND MAIN |
| | DISCONNECTING MEANS. NEC 110.22, 110.16, 110.22 |
| | |
| | 4) PLEASE INDICATE COMPLIANCE WITH FBC-ENERGY. |
| | ELECTRICAL POWER AND LIGHTING SYSTEMS. (MANDATORY) |
| | SECTION 505 |
| | A) INTERIOR LIGHTING CONTROLS. EACH AREA ENCLOSED BY |
| | WALLS OR FLOOR-TO-CEILING PARTITIONS SHALL HAVE AT |
| | LEAST ONE CONTROL DEVICE TO INDEPENDENTLY CONTROL THE |
| | GENERAL LIGHTING WITHIN THE SPACE. EACH MANUAL DEVICE |
| | SHALL BE READILY ACCESSIBLE AND LOCATED SO THE |
| | OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. 505.2.1 |
| | B) BUILDINGS LARGER THAN 5000SQ.FT. SHALL BE EQUIPPED |
| | WITH AN AUTOMATIC CONTROL DEVICE TO SHUT OFF LIGHTING |
| | IN THOSE AREAS. THIS AUTOMATIC CONTROL DEVICE SHALL |
| | FUNCTION ON EITHER; |
| | 1) A SCHEDULED BASIS, USING TIME OF DAY, WITH AN |
| | INDEPENDENT PROGRAM SCHEDULE THAT CONTROLS THE INTERIOR |
| | LIGHTING IN THE AREAS THAT DO NOT EXCEED 25000SQFT AND |
| | ARE NOT MORE THAN ONE FLOOR; OR |
| | 2) AN OCCUPANT SENSOR THAT SHALL TURN LIGHTING OFF |
| | WITHIN 30 MINUTES OF AN OCCUPANT LEAVING A SPACE; OR |
| | 3) A SIGNAL FROM ANOTHER CONTROL OR ALARM SYSTEM THAT |
| | INDICATES THE AREA IS UNOCCUPIED. 505.2.2, |
| | C) PROVIDE A LIGHTING DENSITY SUMMARY ON THE PLAN |
| | SHOWING COMPLIANCE WITH THE FBC ENERGY 505.5.3 |
| | |
| | SEPARATE PERMITS WITH SHOP DRAWINGS REQUIRED FOR FIRE |
| | ALARM, SECURITY, CCTV, AUDIO/VIDEO, NETWORK, AND SIGNS. |
| | |