2014-06-04 17:08:33PLUMBING PROVISO:
 SHEET P1& P2 INDICATE THE USE OF FLOOR DRAINS IN THE
 RESTROOMS. THE PLUMBING FIXTURE SPECIFICATIONS, C FLOOR
 DRAINS ZURN 415 DOES NOT INDICATE THE USE OF A TRAP
 PRIMER AS REQUIRED BY THE 2010 FBC-PLUMBING CODE 1002.4
 TRAP SEALS.
 EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS
 THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102
 MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO
 ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO
 LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE
 INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE
 TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A
 TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR
 ASSE 1044.
  