| 2014-06-04 17:08:33 | PLUMBING PROVISO: | | | SHEET P1& P2 INDICATE THE USE OF FLOOR DRAINS IN THE | | | RESTROOMS. THE PLUMBING FIXTURE SPECIFICATIONS, C FLOOR | | | DRAINS ZURN 415 DOES NOT INDICATE THE USE OF A TRAP | | | PRIMER AS REQUIRED BY THE 2010 FBC-PLUMBING CODE 1002.4 | | | TRAP SEALS. | | | EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS | | | THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 | | | MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO | | | ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO | | | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE | | | INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE | | | TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A | | | TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR | | | ASSE 1044. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|