| Plan Review Notes For Permit 14060093 |
| Permit Number |
14060093 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-01 13:00:12 | DATE: 7/1/2014 | | | PROJECT: THE VITAMIN SHOPPE | | | PERMIT#: 14060093 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 EDITION OF THE FBC | | | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, | | | ADMINISTRATION, 2012 FBC SUPPLEMENTS. | | | | | | 1ST ELECTRICAL PLAN REVIEW | | | ACTION:PROVISO | | | | | | 1) THE INTERIOR OF AN UNDERGROUND RACEWAY SHALL BE | | | CONSIDERED A WET LOCATION. ALL CONDUCTORS WITHIN THE | | | RACEWAY SHALL BE LISTED ACCORDINGLY. SUITABILITY FOR | | | INSTALLATION AND USE IN CONFORMITY WITH THE PROVISIONS | | | OF THIS CODE. NEC 110.3(A)(1 THRU 8) | | | | | | 2) A SEPARATE ELECTRICAL PERMIT APPLICATION SHALL BE | | | SUBMITTED ACCOMPANIED BY SHOP DRAWINGS, EQUIPMENT | | | SUBMITTALS, PRODUCT APPROVALS FOR ALL OF THE FOLLOWING: | | | NETWORK, DATA/COM, FIRE ALARM, SECURITY, CCTV, AND | | | AUDIO/ VIDEO WORK. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] | | | |
|