| 2014-10-28 14:55:11 | TO RM'S DESK |
| | |
| | |
| 2014-10-28 14:14:20 | 10/28/2014 |
| | PROJECT: 249 ALPINE RD |
| | PERMIT#: 14060052 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | |
| | PROVIDE REVISED PLANS TO INDICATE COMPLIANCE WITH THE |
| | FOLLOWING TWO ITEMS PRIOR TO ROUGH INSPECTION: |
| | 1) INDICATE LOCATION OF ELECTRICAL PANELS. THE PLAN |
| | NOTES THE LOCATION TO BE IN THE UTILITY RM BUT THERE IS |
| | NO INDICATION OF AN ELECTRICAL PANEL IN THE UTILITY RM. |
| | THE LOCATION MUST SHOW COMPLIANCE WITH THE |
| | NEC 110.26 |
| | |
| | 2) THE LOAD CALCULATION AND PANEL SCHEDULES INDICATE |
| | THE EXISTANCE OF "SUB-PANEL A". INDICATE THE LOCATION |
| | OF SUB-PANEL A ON THE FLOOR PLAN AND HOW SUB-PANEL A IS |
| | FED AND WITH WHAT ON A REVISED RISER DIAGRAM. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |