| 2014-09-16 10:13:21 | PLAN REVIEW COMMENTS |
| | |
| | |
| | 2ND REVIEW: FBC 2010 |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | MECHANICAL |
| | |
| | 1) FBC-R M1602.2 PROHIBITED SOURCES. |
| | |
| | OUTDOOR AND RETURN AIR FOR A FORCED-AIR HEATING OR |
| | COOLING SYSTEM SHALL NOT BE TAKEN FROM THE FOLLOWING |
| | LOCATIONS: |
| | 2. WHERE FLAMMABLE VAPORS ARE PRESENT; OR WHERE LOCATED |
| | LESS THAN 10 FEET (3048 MM) ABOVE THE SURFACE OF ANY |
| | ABUTTING PUBLIC WAY OR DRIVEWAY; OR WHERE LOCATED AT |
| | GRADE LEVEL BY A SIDEWALK, STREET, ALLEY OR DRIVEWAY. |
| | 5. A ROOM OR SPACE CONTAINING A FUEL-BURNING APPLIANCE |
| | WHERE SUCH ROOM OR SPACE SERVES AS THE SOLE SOURCE OF |
| | RETURN AIR. |
| | EXEPTIONS: |
| | 1. THE FUEL-BURNING APPLIANCE IS A DIRECT-VENT |
| | APPLIANCE OR AN APPLIANCE NOT REQUIRING A VENT IN |
| | ACCORDANCE WITH SECTION M1801.1 OR CHAPTER 24. |
| | 2. THE ROOM OR SPACE COMPLIES WITH THE FOLLOWING |
| | REQUIREMENTS: |
| | 2.1. THE RETURN AIR SHALL BE TAKEN FROM A ROOM OR SPACE |
| | HAVING A VOLUME EXCEEDING 1 CUBIC FOOT FOR EACH 10 |
| | BTU/H (9.6 L/W) OF COMBINED INPUT RATING OF ALL |
| | FUEL-BURNING APPLIANCES THEREIN. |
| | 2.2. THE VOLUME OF SUPPLY AIR DISCHARGED BACK INTO THE |
| | SAME SPACE SHALL BE APPROXIMATELY EQUAL TO THE VOLUME |
| | OF RETURN AIR TAKEN FROM THE SPACE. |
| | 2.3. RETURN-AIR INLETS SHALL NOT BE LOCATED WITHIN 10 |
| | FEET (3048 MM) OF ANY APPLIANCE FIREBOX OR DRAFT HOOD |
| | IN THE SAME ROOM OR SPACE. |
| | |
| | THE UTILITY ROOM IN WHICH THE AIR HANDLER IS LOCATED |
| | CONTAINS A TANKLESS GAS WATER HEATER. THE MECHANICAL |
| | PLANS SPECIFY A LOUVERED DOOR SO THAT RETURN AIR CAN |
| | ENTER THE ROOM MAKING THE ROOM CONTAINING THE GAS WATER |
| | HEATER A PLENUM. ( THE DOOR SCHEDULE ON THE FLOOR PLANS |
| | SPECIFY A HOLLOW CORE DOOR. ) |
| | |
| | 2) SUBMIT THE MANUFACTURER'S INSTALLATION INSTRUCTIONS |
| | AND CONDITIONS OF THE LISTING FOR THE TANKLESS GAS |
| | WATER HEATER. FBC R G2406 (303.1) |
| | |
| | IN ORDER TO REDUCE PLAN REVIEW TIMES, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | |
| | |