| 2014-09-10 11:26:22 | DATE: 9/10/2014 |
| | PROJECT: 249 ALPINE RD |
| | PERMIT#: 14060052 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) A RISER DIAGRAM IS REQUIRED TO INDICATE THE LOCATION |
| | OF THE SERVICE ENTRANCE DISCONNECTING MEANS. PROVIDE A |
| | MAIN SERVICE DISCONNECT AT A READILY ACCESSIBLE |
| | LOCATION NEAREST THE POINT OF ENTRANCE OF THE SERVICE |
| | CONDUCTORS. NEC 230.70, NEC 215.5, WPB AMENDMENTS TO |
| | THE FBC 107.3.5, |
| | |
| | 2) A PANEL SCHEDULE IS REQUIRED TO INDICATE THE CIRCUIT |
| | OCPD SIZE AND CIRCUIT NUMBER. FLOOR PLAN TO BE |
| | IDENTIFIED WITH THE CIRCUIT NUMBERS CORESPONDING TO THE |
| | PANEL SCHEDULE IN ORDER TO DETERMINE THE CIRCUIT AND |
| | WIRE SIZES CORESPONDING TO THE OUTLET OR EQUIPMENT |
| | CONNECTED. NEC 215.5, WPB AMENDMENTS TO THE FBC 107.3.5 |
| | |
| | 3) CARBON MONOXIDE DETECTORS REQUIRED WITHIN 10' OF |
| | SLEEPING AREA. FBC 315 |
| | |
| | 4) ALL 125V SINGLE PHASE, 15 AND 20AMP RECEPTACLES |
| | INSTALLED IN THE LOCATIONS SPECIFIED IN (1) THROUGH (8) |
| | SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION |
| | FOR PERSONNEL. ALL OUTLETS IN THE GARAGE SHALL BE GFCI |
| | PROTECTED INCLUDING THE GDO OUTLET. |
| | |
| | 5) PLANS FAIL TO INDICATE COMPLIANCE WITH SECTION |
| | 210.11 (C)(3) BATHROOM BRANCH CIRCUITS IN ADDITION TO |
| | THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS |
| | OF THIS SECTION, AT LEAST ONE 20-AMPERE BRANCH CIRCUIT |
| | SHALL BE PROVIDED TO SUPPLY BATHROOM RECEPTACLE |
| | OUTLET(S). SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS. |
| | |
| | 6) LUMINAIRES IN CLOTHES CLOSETS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE PROVISIONS OF THE NEC 410.16(A) AND |
| | (B). VERIFY THIS CRITERIA IS MET IN ALL CLOTHES CLOSETS |
| | WITH LUMINAIRES. |
| | |
| | 7) SUFFICIENT ACCESS AND WORKING SPACE SHALL BE |
| | PROVIDED AND MAINTAINED ABOUT ALL ELECTRICAL EQUIPMENT |
| | TO PERMIT READY AND SAFE OPERATION AND MAINTENANCE OF |
| | SUCH EQUIPMENT. NEC 110.26 |
| | VERIFY THIS CRITERIA IS MET AT THE ELECTRICAL PANEL IN |
| | THE HALLWAY ENTRANCE AND AT ALL ELECTRICAL EQUIPMENT |
| | REQUIRING ACCESS FOR SERVICE AND MAINTENANCE. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO |
| | SUBMITTAL PACKAGE AND LEAVE THE PREVIOUSLY REVIEWED |
| | SHEETS FOR COMPARATIVE REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |