| Date |
Text |
| 2014-09-22 15:17:37 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) PROVIDE BUCK DETAILS FOR THE OVER HEAD GARAGE DOOR, |
| | EXTERIOR DOORS AND WINDOWS. FBC R612.10.2.1 |
| | |
| | 2) SHEET A-1 OF THE PLANS HAS WHITE-OUT IN TWO |
| | LOCATIONS. SIGNED AND SEALED PLANS ARE NOT ALLOWED TO |
| | BE ALTERED IN THIS MANNER. FBC 107.1, FS 471 AND FS 481 |
| | |
| | 3) PROVIDE A ROOF FRAMING PLAN THAT SPECIFIES THE |
| | ANCHORS/UPLIFT (ROOF TO WALL CONNECTIONS) FOR THE NEW |
| | ROOF TRUSSES AND GIRDERS. FBC 107.3.5.3 |
| | |
| | 4) THE TRUSS PLANS SPECIFY A 24" WOOD GIRDER THAT HAS |
| | THREE POINT BEARING. THE ARCHITECTURAL PLANS SHOW ONE |
| | END OF THIS GIRDER BEARING ON AN EXTERIOR WALL ABOVE |
| | THE KITCHEN WINDOWS. THE INTERMEDIATE BEARING POINT IS |
| | NOT IDENTIFIED AND THE OTHER END APPEARS TO BE WHERE |
| | THE TRUSS LAYOUT PLAN HAS THE MID-POINT BEARING. |
| | PROVIDE STRUCTURAL DETAILS AND SECTIONS OF THE BEARING |
| | WALLS THAT SUPPORT THIS GIRDER TRUSS. SHOW IN DETAIL |
| | HOW THE LOADS WILL BE SAFELY SUPPORTED AND TRANSFERED |
| | FROM THE ROOF TO THE FOUNDATION. FBC R301.1 |
| | |
| | 5) THE TRUSS LAYOUT AND DRAWINGS FROM THE DELEGATED |
| | ENGINEER ARE REQUIRED TO BE REVIEWED AND APPROVED BY |
| | THE DESIGNER OF RECORD. A SHOP DRAWING REVIEW STAMP |
| | APPROVING THE TRUSS LAYOUT AND DESIGN FROM THE DESIGNER |
| | OF RECORD IS REQUIRED ON THE TRUSS LAYOUT. FAC |
| | 61G15-30.005 & 61G15-31.003 |
| | |
| | 6) THE DIMENSIONS ON THE PLANS INDICATE THAT IT IS 33' |
| | FROM THE OUTSIDE OF THE WALLS SUPPORTING THE LONGER |
| | TRUSSES WHICH ARE SPECIFIED AS 32' 9" LONG (NOT |
| | INCLUDING THE OVERHANG). THE DIMENSIONS FOR THE OTHER |
| | AREA THAT IS RECEIVING THE NEW TRUSSES ARE NOT |
| | INDICATED ON THE PLANS. |
| | |
| | 7) THE INTERIOR BEARING WALL BETWEEN THE BATHROOM AND |
| | BEDROOM IS NOT SPECIFIED AS SUCH ON THE PLANS. THIS |
| | SECTION OF WALL WAS NOT A BEARING WALL. PROVIDE DETAILS |
| | TO SHOW HOW IT WILL BE CONVERTED TO A BEARING WALL. FBC |
| | 107.2.1.3 |
| | |
| | 8) THE COLUMN DETAIL ON SHEET A-1 IS MISSING |
| | INFORMATION, SUCH AS, THE POST SIZE AND WALL THICKNESS, |
| | THE WELD TYPES AT END PLATES, THE LENGTH / EMBED DEPTH |
| | OF THE ANCHOR AND LAG BOLTS. ALSO, IT IS NOT CLEAR ON |
| | THE PLANS WHAT THIS COLUMN IS SUPPORTING. FBC 107.2.1 & |
| | 107.2.1.3 |
| | |
| | 9) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | POLYFOAM ROOF TILE ADHESIVE AS REQUIRED BY DCA RULE |
| | 9N-3. |
| | |
| | 10) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 107.3.4.1 |
| | |
| | 11) SUBMIT CALCULATIONS FOR INDOOR COMBUSTION AIR FOR |
| | THE TANK-LESS GAS WATER HEATER LOCATED IN THE UTILITY |
| | CLOSET. FBCR G2407 (304) THIS COMMENT NEEDS TO BE |
| | ADDRESSED BEFORE THIS PERMIT IS ISSUED. THE MECHANICAL |
| | PLANS CALL FOR A LOUVERED DOOR TO THIS ROOM AND THE |
| | DOOR SCHEDULE ON THE ARCHITECTURAL PLANS SPECIFY A |
| | SOLID DOOR. SEE MECHANICAL COMMENTS. |
| | |
| | 12) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE |
| | SIGNED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION |
| | 405.4.2 |
| | |
| | IN ORDER TO HELP SPEED THE REVIEW PROCESS, PLEASE |
| | SUBMIT A RESPONSE LETTER THAT INDICATES HOW EACH OF THE |
| | REVIEW COMMENTS WAS ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |