| 2014-06-21 12:17:16 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) PROVIDE THE WIND DESIGN DATA ON THE PLANS. SPECIFY |
| | WIND SPEED AND EXPOSURE CATEGORY. ( 170 MPH, EXPOSURE C |
| | ) FBC R301.2.1 |
| | |
| | 2) SPECIFY THE COMPONENT AND CLADDING PRESSURES FOR THE |
| | EXTERIOR OPENINGS WHERE THE NEW WINDOWS AND EXTERIOR |
| | DOORS WILL BE INSTALLED. FBC R301.2.1 |
| | |
| | 3) SPECIFY THE SIZE OF THE NEW OVERHEAD GARAGE DOOR ON |
| | THE PLANS. FBC R301.2.1 |
| | |
| | 4) PROVIDE BUCK DETAILS FOR THE OVER HEAD GARAGE DOOR, |
| | EXTERIOR DOORS AND WINDOWS. FBC R612.10.2.1 |
| | |
| | 5) SUBMIT TWO SETS OF STRUCTURAL PLANS AND DETAILS FOR |
| | THE ROOF TRUSSES AND GIRDER. FBC R801.2 |
| | |
| | 6) PROVIDE AN ELEVATION PLAN FOR THE ROOF SHOWING THE |
| | ROOF SLOPE. CITY AMENDMENTS 107.2.1 & FBC R301.2.1 |
| | |
| | 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | ROOFING MATERIALS AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY |
| | AMENDMENTS 107.3.4.1 |
| | |
| | 9) SUBMIT CALCULATIONS FOR INDOOR COMBUSTION AIR FOR |
| | THE TANKLESS GAS WATER HEATER LOCATED IN THE UTILITY |
| | CLOSET. FBCR G2407 (304) |
| | |
| | 10) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE |
| | SIGNED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION |
| | 405.4.2 |
| | |
| | 11) FLORIDA PRODUCT APPROVAL FL1112-R3 WAS SUBMITTED |
| | FOR A SINGLE OUTSWING DOOR. PLEASE CLARIFY THE DOOR |
| | THAT THIS APPROVAL IS FOR. CITY AMENDMENTS 107.2.1 |
| | |
| | 12) A PGT DIRECTORY WITH PGT SH 400/500 WINDOWS |
| | HI-LIGHTED WAS SUBMITTED. THIS IS NOT A PRODUCT |
| | APPROVAL. IF YOU WISH TO USE THIS PRODUCT IN ADDITION |
| | TO THE PGT 700 SERIES SH WINDOWS, SUBMIT TWO COPIES OF |
| | THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 13) AT THE BOTTOM OF SHEET A-1 THERE IS A NOTE THAT |
| | READS DESIGNER OF RECORD WITH A BLANK SPACE AND THE |
| | NAME JOHN A. PAGLIARULO PRINTED BELOW. PLEASE REMOVE |
| | THIS FROM THE PLANS. THE DESIGNER OF RECORD IS THE |
| | ARCHITECT THAT SIGNED AND SEALED THE PLANS. FS 481 |
| | |
| | 14) IN ORDER TO HELP SPEED THE REVIEW PROCESS, PLEASE |
| | SUBMIT A RESPONSE LETTER THAT INDICATES HOW EACH OF THE |
| | REVIEW COMMENTS WAS ADDRESSED. |
| | |