| 2014-07-03 13:57:09 | PLUMBING PLAN REVIEW |
| | PERMIT:14060022 |
| | ADD: 1815 PALM BEACH LAKES SUITE # E-02 |
| | CONT: TBD |
| | TEL: (561)348-4805 LEXI |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 03/2014 |
| | ACTION: PROVISO |
| | PLUMBING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) THE FUEL GAS WILL REQUIRE A SEPARATE PERMIT. SHEET |
| | P4 PROVIDES A GAS ISOMETRIC PLAN, MISSING INFORMATION |
| | IS FUEL GAS TABLE FROM THE |
| | 2010 FBC-FUEL GAS CODE THAT SYSTEM WAS SIZED FROM, THE |
| | TABLE WILL ALSO PROVIDE THE TYPE OF MATERIAL TO BE |
| | INSTALLED. THIS REVIEW WAS COMPLETED BY USING THE TABLE |
| | 402.4.2 NATURAL GAS, SCHEDULE 40 METALLIC PIPE, LESS |
| | THAN 2 PS, GOOD FOR 300 FT/ 3 INCH = 1,800,000CFH. |
| | A REVISION IS REQUIRED BEFORE THE INSTALLATION OF THE |
| | FUEL GAS SYSTEM BEGINS. |
| | |
| | 2) COMPLETED (/17/2014 PROVIDED CALCULATIONS ). |
| | |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |