| Plan Review Notes For Permit 14060022 |
| Permit Number |
14060022 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-08 15:23:17 | PLAN DENIED | | | | | | 1) KITCHEN EXHAUST HOODS AND COOLERS REQUIRE | | | THERE SEPARATE APPLICATION, PLANS AND PERMIT. | | | PER SECTION 107 FBC 2010 | | | 2) SHOW RTU 1,2,3,AND 4 ON THE PLAN | | | PER SECTION 107 FBC 2010 | | | 3) PROVIDE AN ENGINEER DETAIL ON EXHAUST | | | FAN CURB TIE DOWN TO ROOF AND EXHAUST FAN | | | TO CURB TIE DOWN. PER SECTION 301.12 WIND RESISTANCE | | | 2010 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|