| 2014-07-03 12:40:13 | BUILDING PLAN REVIEW |
| | PERMIT:14060022 |
| | ADD: 1815 PALM BEACH LAKES SUITE # E-02 |
| | CONT: TBD |
| | TEL: (561)348-4805 LEXI |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: THURS. JULY 03/2014 |
| | ACTION: PROVISO |
| | BUILDING APPROVED WITH EXCEPTION! |
| | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO |
| | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO |
| | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE |
| | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE |
| | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. |
| | |
| | 1) SHEET T 1 INDICATES THE WIND SPEED DESIGN IS 140 |
| | MPH. PLEASE NOTE THE WIND DESIGN SPEED FOR THIS |
| | LOCATION IS 170 MPH/ VULT, |
| | 3 SECOND GUST. THIS TRANSLATES INTO 132 MPH/ VASD, 3 |
| | SECOND GUST. THE SHELL IS COMPLETED UNDER THE 170 VASD. |
| | THE WIND DESIGN WILL NEED TO BE CORRECTED BEFORE THE |
| | MECHANICAL EXHAUST FANS AND OR OTHER ROOF TOP EQUIPMENT |
| | ARE ATTACHED TO THE BUILDING ENSURING THE PROPER |
| | ANCHORING OF SYSTEMS INTO THE MAIN WIND FORCE RESISTING |
| | SYSTEMS. 2010 FBC-B FIGURE 1609A ULTIMATE WIND DESIGN |
| | SPEEDS FOR RISK CATEGORY II BUILDINGS. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |