| 2014-07-01 17:03:11 | DATE: 7/1/2014 |
| | PROJECT: ELIZABETH FOUNTAIN INTERIORS |
| | PERMIT#: 14060003 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT |
| | DETAIL AND GROUNDING DETAIL. COMPLETE LOAD |
| | CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON |
| | FLOOR PLAN. FBC-R 107.3.5.3 |
| | PANEL SCHEDULE FOR PANEL MDP DOES NOT INCLUDE THE |
| | CIRCUIT OR THE LOAD FOR PANEL "A" PLEASE ADJUST THE |
| | PANEL SCHEDULE SO THE LOAD FOR PANEL "A" IS INCLUDED IN |
| | THE PANEL SCHEDULE AND THE LOAD CALCULATION. |
| | |
| | 2) THERE ARE SEVERAL 120V LOADS INDICATED ON "B" PHASE |
| | WHICH IS A HIGH LEG RATED AT APPROXIMATELY 208V TO |
| | GROUND. PLEASE ADJUST THE PANEL SCHEDULE SO THE 120V |
| | LOADS ARE INDICATED ON THE APPROPRIATE PHASE. |
| | |
| | 3) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. NEC 422.52 |
| | |
| | 4)THE PROVISIONS OF PART II ARE INTENDED TO REQUIRE |
| | DISCONNECTING MEANS CAPABLE OF DISCONNECTING AIR |
| | CONDITIONING AND REFRIGERATING EQUIPMENT, INCLUDING |
| | MOTOR COMPRESSORS |
| | AND CONTROLLERS FROM THE CIRCUIT CONDUCTORS. NEC 440.11 |
| | SEE ALSO 440.12(A) AND 44.12(A)(1) AND (2) THERE IS NO |
| | CIRCUIT, LOAD DESIGNATION, DISCONNECT OR REQUIRED |
| | RECEPTACLE OUTLET INDICATED ON THE PLANS FOR THE |
| | EXISTING CU ON THE SW CORNER OF THE BUILDING. |
| | |
| | 5) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI |
| | RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE |
| | LOCATION FOR THE SERVICING OF HEATING, |
| | AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE |
| | RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND |
| | WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND |
| | REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL |
| | NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT |
| | DISCONNECTING MEANS. NEC 210.63 SEE ALSO 210.8(A)(3) . |
| | ALL 15 AND 20AMP, 125V AND 250V RECEPTACLES INSTALLED |
| | IN IN A WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS |
| | WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS |
| | INSERTED. ALL 15- AND 20-AMPERE, 125- AND 250-VOLT |
| | NON-LOCKING RECEPTACLES SHALL BE LISTED |
| | WEATHER-RESISTANT TYPE. NEC 406.8(B)(1) THIS IS JUST |
| | NOTED FOR THE REQUIRED OUTLETS AT THE RTU AND EXISTING |
| | CU THAT ARE LOCATED OUTDOORS. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |