Plan Review Notes
Plan Review Notes For Permit 14060003
Permit Number 14060003
Review Stop E
Sequence Number 1
Notes
Date Text
2014-07-01 17:03:11DATE: 7/1/2014
 PROJECT: ELIZABETH FOUNTAIN INTERIORS
 PERMIT#: 14060003
 CODE: 2008 EDITION OF THE NEC
 2010 EDITION OF THE FBC
 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
  
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT
 DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. FBC-R 107.3.5.3
 PANEL SCHEDULE FOR PANEL MDP DOES NOT INCLUDE THE
 CIRCUIT OR THE LOAD FOR PANEL "A" PLEASE ADJUST THE
 PANEL SCHEDULE SO THE LOAD FOR PANEL "A" IS INCLUDED IN
 THE PANEL SCHEDULE AND THE LOAD CALCULATION.
  
 2) THERE ARE SEVERAL 120V LOADS INDICATED ON "B" PHASE
 WHICH IS A HIGH LEG RATED AT APPROXIMATELY 208V TO
 GROUND. PLEASE ADJUST THE PANEL SCHEDULE SO THE 120V
 LOADS ARE INDICATED ON THE APPROPRIATE PHASE.
  
 3) ELECTRIC DRINKING FOUNTAINS SHALL BE PROTECTED WITH
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. NEC 422.52
  
 4)THE PROVISIONS OF PART II ARE INTENDED TO REQUIRE
 DISCONNECTING MEANS CAPABLE OF DISCONNECTING AIR
 CONDITIONING AND REFRIGERATING EQUIPMENT, INCLUDING
 MOTOR COMPRESSORS
 AND CONTROLLERS FROM THE CIRCUIT CONDUCTORS. NEC 440.11
 SEE ALSO 440.12(A) AND 44.12(A)(1) AND (2) THERE IS NO
 CIRCUIT, LOAD DESIGNATION, DISCONNECT OR REQUIRED
 RECEPTACLE OUTLET INDICATED ON THE PLANS FOR THE
 EXISTING CU ON THE SW CORNER OF THE BUILDING.
  
 5) ONE 125VOLT, SINGLE-PHASE, 15 OR 20AMP GFI
 RECEPTACLE OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE
 LOCATION FOR THE SERVICING OF HEATING,
 AIR-CONDITIONING, AND REFRIGERATION EQUIPMENT. THE
 RECEPTACLE SHALL BE LOCATED ON THE SAME LEVEL AND
 WITHIN 25FT OF THE HEATING, AIR-CONDITIONING, AND
 REFRIGERATION EQUIPMENT. THE RECEPTACLE OUTLET SHALL
 NOT BE CONNECTED TO THE LOAD SIDE OF THE EQUIPMENT
 DISCONNECTING MEANS. NEC 210.63 SEE ALSO 210.8(A)(3) .
 ALL 15 AND 20AMP, 125V AND 250V RECEPTACLES INSTALLED
 IN IN A WET LOCATION SHALL HAVE AN ENCLOSURE THAT IS
 WEATHERPROOF WHETHER OR NOT THE ATTACHMENT PLUG CAP IS
 INSERTED. ALL 15- AND 20-AMPERE, 125- AND 250-VOLT
 NON-LOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE. NEC 406.8(B)(1) THIS IS JUST
 NOTED FOR THE REQUIRED OUTLETS AT THE RTU AND EXISTING
 CU THAT ARE LOCATED OUTDOORS.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  