| 2014-06-03 13:51:53 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | THIS PLAN IS APPROVED PENDING THE APPROVAL OF BUILDING | | | AND ELECTRICAL REVIEWS. | | | | | | THIS APPROVAL DOES NOT CONSTITUTE APPROVAL OF THE | | | SEATING, BUFFET AND EQUIPMENT PLAN. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | PROVIDE TYPE K EXTINGUISHERS WHEN COOKING WITH GREASE | | | OR WHEN PRODUCING SMOKE OR GREASE-LADEN VAPORS. | | | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | | BUILDING STRUCTURES. | | | | | | TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | GENERATORS AND OTHER INTERNAL COMBUSTION POWER SOURCES | | | SHALL BE SEPARATED FROM TENTS BY A MINIMUM OF 5 FEET | | | AND SHALL BE PROTECTED FROM CONTACT BY FENCING OR | | | ENCLOSURE. | | | | | | | | 2014-05-30 10:37:21 | ROUTED TO FIRE |
|