2014-09-02 16:39:34****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 1609, WIND DESIGN CRITERIA WAS STATED AS
 V=115MPH, HIGH VELOCITY HURRICANE ZONE.
  
 PLEASE REVISE. ONLY BROWARD AND DADE COUNTIES ARE
 LOCATED IN THE HVHZ. PALM BEACH MINIMUM DESIGN CRITERIA
 FOR THE COLUMNS (STRUCTURES) WOULD BE 150MPH, VULT
 (RISK CATEGORY I). THERE IS NO WIND DESIGN CRITERIA FOR
 FENCES IN NON-HVHZ. MY APOLOGIES FOR MY PREVIOUS
 COMMENT NOT BEING CLEAR THAT IT PERTAINED ONLY TO THE
 COLUMNS.
  
 IF THIS PROJECT IS TIME SENSITIVE, NEXT REVIEW WILL BE
 EXPEDITED (NO FEE) UPON REQUEST DUE TO THE AMBIGUITY OF
 THE PREVIOUS COMMENT. PLEASE REQUEST VIA EMAIL.
  
  