| 2014-06-19 11:19:43 | ON PAGE E4 I NOTICED A SPACE ON THE PANEL SCHEDULE AS | | | "NOT LABELED", SO I MADE THE FOLLOWING NOTE: | | | PER NEC 408.4, ALL CIRCUITS SHALL BE LABELED AND | | | IDENTIFIED. SPARE SPACES CONTAINING UN-USED BREAKERS | | | SHALL BE DESCRIBED ACCORDINGLY. THERE SHALL BE NO | | | UNLABELED OCPD'S. | | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | | PLANS EXAMINER | | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | | FOLLOWING LINK: | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | | ABOVE THE SECOND PERMIT INFORMATION). | | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR | | | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER | | | PERMIT CONDITIONS. | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME | | | AT (561) 805-6718 OR EMAIL: [email protected], OR | | | DAVID HAYES AT: [email protected], OR (561) 805-6717. | | | THANK YOU. | | | |
|