| Plan Review Notes For Permit 14051052 |
| Permit Number |
14051052 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-12 15:17:40 | 1. 12 X 12 DUCT THRU WALL FROM A.H.U- 1 , ITS A FIRE- | | | RATED WALL CONDITION. | | | 2. PROVIDE OUTSIDE AIR ON PLANS TYP. | | | 3. SHOW ON PLANS EXH. DUCT DIAMETER TYP. | | | 4. SHOW ON PLANS EXTRACTORS ON DUCTWORK SYSTEM. | | | 5. A.H.U. DETAIL SHOW FLOAT SWITCH. | | | 6. PROVIDE O/A CALCULATION. | | | 7. PROVIDE HVAC DESIGN REQUIRMENTS. | | | 8. PROVIDE APPROVED EQUIPMENT STANDS DETAIL. | | | 9. NOTE CHANGED TO CU-S. |
|