| Plan Review Notes For Permit 14051052 |
| Permit Number |
14051052 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-18 16:02:30 | *PROVIDE ELECTRICAL LOAD CALCULATION FOR EXISTING & | | | ADDITIONAL LOADS FOR LUMINIAIRES & DRINKING FOUNTAIN. | | | (2010 FBC 107.3.5, 2008 NEC ART 220, 2008 NEC 220.14(A) | | | & (B)) | | | | | | *PROVIDE WIRING METHODS, MATERIALS AND CIRCUITRY FOR | | | ADDITIONAL WIRING | | | (2010 FBC 107.3.5) | | | | | | *EXISTING DUPLEX RECEPTACLES LOCATED IN NEWLY FURR | | | WALLS MUST BE EXTENDED OR RELOCATED | | | NOTE PLANS FOR METHOD OF COMPLIANCE. | | | (2008 NEC 314.20) | | | | | | K SWIERZKO (561) 805-6700 |
|