2014-07-18 16:02:30*PROVIDE ELECTRICAL LOAD CALCULATION FOR EXISTING &
 ADDITIONAL LOADS FOR LUMINIAIRES & DRINKING FOUNTAIN.
 (2010 FBC 107.3.5, 2008 NEC ART 220, 2008 NEC 220.14(A)
 & (B))
  
 *PROVIDE WIRING METHODS, MATERIALS AND CIRCUITRY FOR
 ADDITIONAL WIRING
 (2010 FBC 107.3.5)
  
 *EXISTING DUPLEX RECEPTACLES LOCATED IN NEWLY FURR
 WALLS MUST BE EXTENDED OR RELOCATED
 NOTE PLANS FOR METHOD OF COMPLIANCE.
 (2008 NEC 314.20)
  