| 2014-06-02 17:09:16 | NOT ENOUGH DETAIL ON THE SUBMITTED DRAWING TO | | | ACCURATELY DETERMINE THE WORK BEING DONE. | | | | | | I WILL NEED THE FOLLOWING ADDED TO THE DRAWINGS FOR A | | | SUCCESSFUL ELECTRICAL REVIEW: | | | | | | 1. IDENTIFY WHICH IS BLDG. FORTON AND BLDG.SANDER | | | 2. PROVIDE A DETAIL DESCRIPTION OF THE PROPOSED FEEDER. | | | 3. SUBMIT A LOAD CALC TO DETERMINE THAT PROPER SIZE OF | | | THE FEEDER. | | | 4. INCLUDE ON THE DRAWING CONDUCTOR SIZING AND | | | INSULATION. | | | | | | THESE PLANS WERE REVIEWED BY MIKE ALBARRAN, ELECTRICAL | | | PLANS EXAMINER | | | YOU ARE WELCOME TO REVIEW STATUS OR COMMENTS AT THE | | | FOLLOWING LINK: | | | | | | HTTP://ONESTOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STAT | | | US.ASPX | | | | | | ENTER YOUR PERMIT NUMBER (SEE SUBJECT LINE OF THIS | | | EMAIL FOR YOUR PERMIT #), CLICK ON THE PERMIT NUMBER, | | | AND THEN GO TO "PLAN REVIEWS" TO SEE YOUR COMMENTS (TAB | | | ABOVE THE SECOND PERMIT INFORMATION). | | | AFTER ISSUANCE, PLEASE CHECK YOUR PLAN CAREFULLY FOR | | | COMPLIANCE WITH ANY REDLINES, NOTES, PROVISOS, OR OTHER | | | PERMIT CONDITIONS. | | | FOR FURTHER ASSISTANCE, PLEASE FEEL FREE TO CONTACT ME. | | | I CAN BE REACHED AT 561-805-6718 OR | | | [email protected] | | | |
|