| 2014-06-13 15:15:41 | PLUMBING PLAN REVIEW |
| | PERMIT: 14050989 |
| | ADD: 207 6TH ST |
| | CONT: FINE LINE CONSTRUCTION |
| | TEL: (561)582-7880 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JUNE 13/2014 |
| | ACTION: DENIED |
| | |
| | 1) THE SANITARY ISOMETRIC IS DRAWN WITH THE RESTROOMS |
| | USING HORIZONTAL WET VENTS. PLEASE SEE THE CODE SECTION |
| | INDICATES WET VENTS ARE TO BE INSTALLED IN BATHROOMS (1 |
| | & 2 FAMILY) ALSO SEE BOAF INFORMAL INTERPRETATION. |
| | |
| | DATE: MON APR 13 2009 |
| | REPORT: 6090 |
| | CODE: PLUMBING CODE YEAR: 2007 |
| | SECTION: 909 |
| | QUESTION: |
| | IS IT THE INTENT OF THE FLORIDA BUILDING CODE - |
| | PLUMBING SECTION 909 TO ALLOW A URINAL TO WET VENT A |
| | SINGLE COMMERCIAL |
| | WATER CLOSET OR TO DRAIN INTO THAT WATER CLOSET?S |
| | INDIVIDUAL VENT? |
| | COMMENT: |
| | ANSWER: |
| | NO. ONLY FIXTURES IN BATHROOM GROUPS AS DEFINED IN |
| | FLORIDA BUILDING CODE - PLUMBING CHAPTER 2 ARE |
| | PERMITTED TO |
| | CONNECT TO THE WET VENT. ANY ADDITIONAL FIXTURES MUST |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | COMMENTARY: |
| | A URINAL IS NOT INCLUDED IN THE DEFINITION OF A |
| | BATHROOM GROUP. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |