| Plan Review Notes For Permit 14050989 |
| Permit Number |
14050989 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-09 16:24:56 | 6/9/14. | | | PROJECT: HOPKINS MARINE. | | | PERMIT#: 14050989 | | | CODE: 2008 EDITION OF THE NEC AND THE 2010 EDITION OF | | | THE FBC | | | ACTION: APPROVED WITH PROVISO: | | | | | | 1) PARTITIONS OF THE FREESTANDING TYPE (NOT FIXED) | | | SHALL BE PERMITTED TO BE CONNECTED TO THE BUILDING | | | ELECTRICAL SYSTEM BY ONE OF THE WIRING METHODS OF | | | CHAPTER 3. MULTIWIRE BRANCH CIRCUITS SUPPLYING POWER TO | | | PERMANENTLY CONNECTED FREESTANDING PARTITIONS SHALL BE | | | PROVIDED WITH A MEANS TO DISCONNECT SIMULTANEOUSLY ALL | | | UNGROUNDED CONDUCTORS AT THE PANELBOARD WHERE THE | | | BRANCH CIRCUIT ORIGINATES. NEC 605.7 | | | | | | 2) EACH MULTIWIRE BRANCH CIRCUIT SHALL BE PROVIDED WITH | | | A MEANS THAT WILL SIMULTANEOUSLY DISCONNECT ALL | | | UNGROUNDED CONDUCTORS AT THE POINT WHERE THE BRANCH | | | CIRCUIT ORIGINATES. 210.4(B) | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR AT [email protected] |
|