| 2014-06-13 15:00:43 | BUILDING PLAN REVIEW |
| | PERMIT: 14050989 |
| | ADD: 207 6TH ST |
| | CONT: FINE LINE CONSTRUCTION |
| | TEL: (561)582-7880 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JUNE 13/2014 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE PROVIDE A SURVEY OF THE PROPERTY, THE SITE |
| | PLAN DOES NOT MATCH TTHE LOT CONFIGURATION FOUND WITH |
| | THE PROPERTY APPRAISERS WEB SITE. |
| | THE SECOND ISSUE IS TO DETERMINE IF THIS BUILDING IS IN |
| | A A5 FLOOD ZONE. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. IF FLOOD ZONE THEN FLOOD ZONE CERTIFICATES |
| | WILL BE REQUIRED AND THE FLOOR ELEVATION OF THE 1ST |
| | FLOOR. |
| | |
| | 2) SHEET A-1.0: |
| | 2A) BOTH THE MENS(125) & WOMENS (126) RESTROOMS HAVE |
| | WITHIN THEM ACCESSIBLE TOLIET COMPARTMENTS (STALLS) |
| | PLEASE SEE 2010 FBC-ACCESSIBLITY CODE SECTION 604.8.1.2 |
| | FOR DOOR SWING. TOILET COMPARTMENT DOORS SHALL NOT |
| | SWING INTO THE MINIMUM REQUIRED COMPARTMENT AREA. THE |
| | DOORS SWING IN OVER THE REQUIED CLEAR AREA FOR THE LAV. |
| | |
| | 2B) NO ACTION TO BE TAKEN. THE PLANS DO NOT PROVIDE |
| | VERTICAL ACCESSIBILITY TO THE MEZZANINE AREA. 201.1.1, |
| | IT APPEARS THE EXCEPTIONS , EXCEPTION # 2 FOR STORAGE |
| | AND EXCEPTION # 3 FOR OCCUPIABLE SPACES AND PRIVATE |
| | OFFICE. |
| | |
| | 3) SHEET S-4.1 SHOWS THE DESIGN LOADS BUT THERE ARE NO |
| | DESIGN LOADS FOR THE STAIRS OR MEZZANINE FOR THE OFFICE |
| | OR THE STORAGE PORTION OF THE MEZZANINE, WILL THE |
| | MEZZANINE BEDESIGNED FOR LIGHT OR HEAVY? FBC-B TABLE |
| | 1607.1. |
| | |
| | 4) PLANS DO NOT SHOW CODE COMPLIANCE WITH 2010 FL |
| | ACCESSIBILTY 211.2 MINIMUM NUMBER. |
| | NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | NOTE NO ROOFING PRODUCT APPROVALS WERE SUBMITTED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |