2014-07-01 16:23:39DATE: 7/1/2014
 PROJECT: NUSSDORF, PENTHOUSE 2G.
 PERMIT#: 14050976
 CODE: 2008 EDITION OF THE NEC
 2010 FLORIDA BUILDING CODE W
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012 FBC
 SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 DUPLICATE COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO
 PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG
 WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY,
 INSERT CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS. TWO SETS REQUIRED.
  
 1) ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT
 DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. FBC 107.3.5.3
  
 2) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. FBC R314, 315
  
 3) A GROUNDING ELECTRODE SYSTEM IS REQUIRED AT THE
 SERVICE. SEE SECTION III OF NEC 250.50
  
 4) AN INTER SYSTEM BOND IS REQUIRED AT THE SERVICE. NEC
 250.94
  
 SEPARATE PERMITS REQUIRED FOR STRUCTURED CABLING,
 NETWORK, SECURITY, AUDIO/VIDEO, CCTV
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421.