| 2014-07-01 16:23:39 | DATE: 7/1/2014 |
| | PROJECT: NUSSDORF, PENTHOUSE 2G. |
| | PERMIT#: 14050976 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 FLORIDA BUILDING CODE W |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012 FBC |
| | SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | DUPLICATE COMMENTS. WHEN RESUBMITTING, IT IS HELPFUL TO |
| | PROVIDE A RESPONSE LETTER ADDRESSING EACH ITEM ALONG |
| | WITH THE CITY RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, |
| | INSERT CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE |
| | PREVIOUSLY REVIEWED SHEETS. TWO SETS REQUIRED. |
| | |
| | 1) ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT |
| | DETAIL AND GROUNDING DETAIL. COMPLETE LOAD |
| | CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON |
| | FLOOR PLAN. FBC 107.3.5.3 |
| | |
| | 2) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. FBC R314, 315 |
| | |
| | 3) A GROUNDING ELECTRODE SYSTEM IS REQUIRED AT THE |
| | SERVICE. SEE SECTION III OF NEC 250.50 |
| | |
| | 4) AN INTER SYSTEM BOND IS REQUIRED AT THE SERVICE. NEC |
| | 250.94 |
| | |
| | SEPARATE PERMITS REQUIRED FOR STRUCTURED CABLING, |
| | NETWORK, SECURITY, AUDIO/VIDEO, CCTV |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421. |