| Plan Review Notes For Permit 14050976 |
| Permit Number |
14050976 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-06-10 16:45:05 | DATE: 6/10/2014 | | | PROJECT: NUSSDORF, PENTHOUSE 2G. | | | PERMIT#: 14050976 | | | CODE: 2008 EDITION OF THE NEC | | | 2010 FLORIDA BUILDING CODE W | | | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING | | | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012 FBC | | | SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | ELECTRICAL PLAN REVIEW | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT | | | DETAIL AND GROUNDING DETAIL. COMPLETE LOAD | | | CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN. FBC 107.3.5.3 | | | | | | 2) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON | | | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH | | | ROOM USED FOR SLEEPING. FBC R314, 315 |
|