2014-06-10 16:45:05DATE: 6/10/2014
 PROJECT: NUSSDORF, PENTHOUSE 2G.
 PERMIT#: 14050976
 CODE: 2008 EDITION OF THE NEC
 2010 FLORIDA BUILDING CODE W
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION 2012 FBC
 SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 ELECTRICAL PLAN REVIEW
  
 1ST REVIEW
 ACTION: DENIED
  
 1) ELECTRIC SERVICE RISER WITH WIRE SIZES, CONDUIT
 DETAIL AND GROUNDING DETAIL. COMPLETE LOAD
 CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON
 FLOOR PLAN. FBC 107.3.5.3
  
 2) REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE RESIDENCE HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. FBC R314, 315