| 2014-06-05 19:18:16 | PLUMBING PLAN REVIEW |
| | PERMIT: 14050974 |
| | ADD: 525 S FLAGLER DR # GPH3 |
| | CONT: CAMBRIDGE CONSTRUCTION |
| | TEL: (561)284-3722 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURSDAY JUNE 05/2014 |
| | ACTION: DENIED |
| | |
| | 1) PLANS SEALED BY OUT OF STATE ARCHITECT. FLORIDA |
| | ADMINISTRATIVE RULE 61G1-16.002 DESCRIPTION OF SEAL. |
| | (1) THE SEAL SHALL CONTAIN THE NAME OF ONLY ONE |
| | ARCHITECT OR INTERIOR DESIGNER AND THE REGISTRATION |
| | NUMBER; THE SEAL OF THE ARCHITECT SHALL BE CIRCULAR, |
| | AND THE SEAL OF THE INTERIOR DESIGNER SHALL BE |
| | HEXAGONAL. BOTH SEALS SHALL BE APPROXIMATELY 2" IN |
| | DIAMETER WITH TWO CIRCULAR LINES BETWEEN WHICH LINES |
| | SHALL APPEAR, AT THE TOP, THE WORDS ?STATE OF FLORIDA? |
| | AND AT THE BOTTOM THE WORDS ?REGISTERED ARCHITECT? OR |
| | ?LICENSED INTERIOR DESIGNER,? WHICHEVER IS APPLICABLE. |
| | |
| | 2) SHEETS D-100 & A-100 SHOW THE REMOVAL OF A TUB AND |
| | NEW LOCATION FOR THE WATER CLOSET & BIDET. THERE IS NO |
| | FLAT SANITARY NOR SANITARY RISER DIAGRAM SHOWING THE |
| | NEW SANITARY PIPING AND VENTING OF THESE FIXTURES. 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION107.3.5 MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.3 PLUMBING |
| | 1. MINIMUM PLUMBING FIXTURE CLEARANCES BIDET TO WATER |
| | CLOSET FBC-P FIGURE 405.3.1. |
| | 2. FIXTURE REQUIREMENTS |
| | 3. WATER SUPPLY PIPING |
| | 4. SANITARY DRAINAGE |
| | 5. VENTS |
| | 6.PLUMBING RISE |
| | |
| | 3) THE SANITARY WASTE WILL BE ROUTED THROUGH THE FLOOR |
| | BELOW HOW WILL THE CONTRACTOR GAIN ENTRY. HOW WILL THE |
| | FLOOR FIRE RATING BE MAINTAINED. |
| | 2010 FBC-P 307.3 PENETRATIONS OF FLOOR/CEILING |
| | ASSEMBLIES AND FIRE-RESISTANCE-RATED ASSEMBLIES. |
| | PENETRATIONS OF FLOOR/CEILING ASSEMBLIES AND ASSEMBLIES |
| | REQUIRED TO HAVE A FIRE-RESISTANCE RATING SHALL BE |
| | PROTECTED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| | BUILDING. |
| | |