| Plan Review Notes For Permit 14050953 |
| Permit Number |
14050953 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2014-07-05 13:21:21 | ****PROVISO**** | | | ****ISSUED AT CONTRACTOR'S RISK**** | | | ****REVISION REQUIRED BEFORE FIRST INSPECTION**** | | | | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected], | | | FBC FLORIDA BUILDING CODE 2010 | | | | | | FBC 1609, SHEET 1 OF 1 SPECIFIES FASTENERS IN ITEM 13 | | | BUT DOES NOT SPECIFY THE NUMBER OF FASTENERS REQUIRED. | | | SUBMIT A REVISION WHICH PROVIDES EITHER NUMBER OF | | | FASTENERS REQUIRED OR A DRAWING SHOWING FASTENER | | | PATTERN. | | | | | | ITEM 11 SPECIFIES THAT LETTERS BOTTOM MOUNT TO RACEWITH | | | REQUIRED FASTENERS. THIS SHOULD SPECIFY FASTENER TYPE, | | | DIAMETER, LENGTH, NUMBER REQUIRED OR FASTENING PATTERN. | | | |
|