| Plan Review Notes For Permit 14050944 |
| Permit Number |
14050944 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-07-28 10:44:29 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FROM PREVIOUS REVIEW: | | | | | | 1. PROVIDE MORE INFORMATION REGARDING THE FLAME | | | RESISTANCE OF THIS PRODUCT. SEE FBC 603.1. THIS | | | APPLICATION WILL BE CONSIDERED BUT MORE INFORMATION IS | | | REQUIRED. | | | | | | PLEASE PROVIDE A COPY OF THE TEST RESULTS WHICH SHOULD | | | INCLUDE THE TEST STANDARD. | | | | | | 2ND REVIEW - | | | | | | TEST STANDARD/TEST RESULT NOT PROVIDED. ONLY THE | | | CERTIFICATE WHICH IS TYPICALLY PROVIDED FOR FABRIC | | | AWNINGS WAS PROVIDED. YOU ARE PROPOSING TO INSTALL A | | | VINYL ENCAPSULATED PRODUCT ON THE ROOFTOP OF A NON | | | COMBUSTIBLE BUILDING. MORE INFORMATION IS REQUIRED. | | | | | | 3RD REVIEW - | | | | | | THE TEST PROVIDED WAS FOR NFPA 701. BASED ON | | | INFORMATION ON THE INTERNET, THIS IS A VINYL | | | ENCAPSULATED FABRIC WHICH HAS BEEN TREATED TO BE FIRE | | | RESISTANT. IN A NON COMBUSTIBLE BUILDING (TYPE I AND | | | TYPE II CONSTRUCTION), NON COMBUSTIBLE MATERIALS ARE | | | REQUIRED EXCEPT AS EXCEPTED IN FBC 602. THIS WAS | | | DISCUSSED WITH THE BUILDING OFFICIAL. | | | | | | PLEASE CHANGE THE MATERIAL PROPOSED TO A | | | NONCOMBUSTIBLE, OR PROVIDE A TEST WHICH DEMONSTRATES | | | THAT THE PROPOSED PRODUCT IS A NON COMBUSTIBLE (NOT | | | FLAME RESISTANT). | | | | | | | | | |
|