| Plan Review Notes For Permit 14050944 |
| Permit Number |
14050944 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-07-11 14:24:15 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FROM PREVIOUS REVIEW: | | | | | | 1. PROVIDE MORE INFORMATION REGARDING THE FLAME | | | RESISTANCE OF THIS PRODUCT. SEE FBC 603.1. THIS | | | APPLICATION WILL BE CONSIDERED BUT MORE INFORMATION IS | | | REQUIRED. | | | | | | PLEASE PROVIDE A COPY OF THE TEST RESULTS WHICH SHOULD | | | INCLUDE THE TEST STANDARD. | | | | | | 2ND REVIEW - | | | | | | TEST STANDARD/TEST RESULT NOT PROVIDED. ONLY THE | | | CERTIFICATE WHICH IS TYPICALLY PROVIDED FOR FABRIC | | | AWNINGS WAS PROVIDED. YOU ARE PROPOSING TO INSTALL A | | | VINYL ENCAPSULATED PRODUCT ON THE ROOFTOP OF A NON | | | COMBUSTIBLE BUILDING. MORE INFORMATION IS REQUIRED. | | | | | | | | | |
|