| 2014-07-17 12:02:22 | DATE: 7/14/2014 |
| | PROJECT: MALVERNE RESIDENCE |
| | PERMIT#: 14050937 |
| | CODE: 2008 EDITION OF THE NEC |
| | 2010 EDITION OF THE FBC |
| | 2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | |
| | 3RD ELECTRICAL PLAN REVIEW |
| | ACTION: PROVISO |
| | |
| | 1) AN INTER SYSTEM BOND IS REQUIRED AT THE SERVICE. NEC |
| | 250.94. |
| | |
| | 2) A SWITCH CONTROLLED LIGHT IS REQUIRED AT THE ATTIC |
| | ACCESS. FOR ATTICS, UNDERFLOOR SPACES, UTILITY ROOMS, |
| | AND BASEMENTS, AT LEAST ONE LIGHTING OUTLET CONTAINING |
| | A SWITCH OR CONTROLLED BY A WALL SWITCH SHALL BE |
| | INSTALLED WHERE THESE SPACES ARE USED FOR STORAGE OR |
| | CONTAIN EQUIPMENT REQUIRING SERVICING. AT LEAST ONE |
| | POINT OF CONTROL SHALL BE AT THE USUAL POINT OF ENTRY |
| | TO THESE SPACES. THE LIGHTING OUTLET SHALL BE PROVIDED |
| | AT OR NEAR THE EQUIPMENT REQUIRING SERVICING. NEC |
| | 210.70(3) |
| | |
| | 3) INDICATE A SMOKE AND C/O DETECTION SYSTEM AS |
| | REQUIRED PER FBC-R 314, 315 |
| | "EVERY SEPARATE BUILDING OR AN ADDITION TO AN EXISTING |
| | BUILDING FOR WHICH A PERMIT FOR NEW CONSTRUCTION IS |
| | ISSUED AND HAVING A FOSSIL-FUEL-BURNING HEATER OR |
| | APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, OR OTHER |
| | FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON MONOXIDE |
| | AS A BYPRODUCT OF COMBUSTION SHALL HAVE AN OPERATIONAL |
| | CARBON MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH |
| | ROOM USED FOR SLEEPING PURPOSES". FBC-R 315.1 |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |