| Plan Review Notes For Permit 14050930 |
| Permit Number |
14050930 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2014-11-05 15:15:10 | DENIED BY ELECTRICAL | | | | | | 1) THE ELECTICAL LOAD CALCULATIONS, THE PANEL SCHEDULE | | | AND THE RISER PLAN SPECIFY A 150 AMP PANEL. THE | | | ELECTRICAL FLOOR PLAN SPECIFIES A 100 AMP PANEL. PLEASE | | | CORRECT. FBC 107.2.1 |
|