| 2014-08-22 07:21:24 | 2010 FBC / 2008 NEC | | | | | | ELECTRICAL DENIED | | | | | | THE NEW 100 AMP PANEL THAT IS SPECIFIED ON THE | | | ELECTRICAL PLAN APPEARS TO BE TOO SMALL FOR THIS SINGLE | | | FAMILY DWELLING. PLEASE ADDRESS THE FOLLOWING COMMENTS. | | | | | | 1) SUBMIT TWO SETS OF LOAD CALCULATIONS AND PANEL | | | SCHEDULE ON THE PLANS. CITY AMENDMENTS 107.3.5.3 | | | | | | 2) PROVIDE AN ELECTRICAL SERVICE RISER DIAGRAM WITH | | | WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL ON THE | | | PLANS. CITY AMENDMENTS 107.3.5.3 | | | | | | 3) SPECIFY THE AIC RATING OF THE ELECTRICAL EQUIPMENT | | | ON THE PLANS. NEC 110.9 | | | | | | 4) THE 2008 NEC IS THE APPLICABLE ELECTICAL CODE FOR | | | THIS PROJECT. PLEASE CORRECT THE REFERENCE TO THE 2013 | | | NEC ON SHEET E-01. | | | | | | 5) THE NOTE IN THE UPPER RIGHT SIDE OF THE PLAN | | | SPECIFIES THE SFBC 2010. THERE IS NO LONGER AN SFBC. | | | THIS SHOULD BE FBC ( FLORIDA BUILDING CODE ) 2010. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|