2014-08-22 07:21:242010 FBC / 2008 NEC
  
 ELECTRICAL DENIED
  
 THE NEW 100 AMP PANEL THAT IS SPECIFIED ON THE
 ELECTRICAL PLAN APPEARS TO BE TOO SMALL FOR THIS SINGLE
 FAMILY DWELLING. PLEASE ADDRESS THE FOLLOWING COMMENTS.
  
 1) SUBMIT TWO SETS OF LOAD CALCULATIONS AND PANEL
 SCHEDULE ON THE PLANS. CITY AMENDMENTS 107.3.5.3
  
 2) PROVIDE AN ELECTRICAL SERVICE RISER DIAGRAM WITH
 WIRE SIZES, CONDUIT DETAIL AND GROUNDING DETAIL ON THE
 PLANS. CITY AMENDMENTS 107.3.5.3
  
 3) SPECIFY THE AIC RATING OF THE ELECTRICAL EQUIPMENT
 ON THE PLANS. NEC 110.9
  
 4) THE 2008 NEC IS THE APPLICABLE ELECTICAL CODE FOR
 THIS PROJECT. PLEASE CORRECT THE REFERENCE TO THE 2013
 NEC ON SHEET E-01.
  
 5) THE NOTE IN THE UPPER RIGHT SIDE OF THE PLAN
 SPECIFIES THE SFBC 2010. THERE IS NO LONGER AN SFBC.
 THIS SHOULD BE FBC ( FLORIDA BUILDING CODE ) 2010.
  