2014-08-22 12:47:202010 FBC
  
 DENIED BY BUILDING
  
 1) THE WIND DESIGN DATA ON SHEET A-01 HAS DIFFERENT
 EXPOSURE CATEGORIES FOR EACH SIDE OF THE STRUCTURE.
 ASCE 7 - 10 SECTION 26.7.4.2 REQUIRES WIND LOADS FOR
 THE DESIGN OF THE MWFRS TO BE BASED ON THE EXPOSURE
 CATEGORY RESULTING IN THE HIGHEST WIND LOADS FOR ANY
 WIND DIRECTION AT THE THE SITE. ASCE 7 - 10 SECTION
 26.7.4.4 REQUIRES DESIGN WIND PRESSURES FOR COMPONENTS
 AND CLADDING TO BE BASED ON THE EXPOSURE CATEGORY
 RESULTING IN THE HIGHEST WIND LOADS FOR ANY WIND
 DIRECTION AT THE THE SITE. THE HIGHEST EXPOSURE
 CATEGORY THAT WAS SPECIFIED ON THE PLANS IS EXPOSURE C.
 THEREFORE, THE DESIGN FOR THE MWFRS AND THE COMPONENT
 AND CLADDING PRESSURES ARE TO BE BASED ON EXPOSURE C.
 PLEASE REVISE THE PLANS.
  
 2) BASED ON FBCR TABLES R301.2(2), R301.2(3) &
 R301.2(4), THE COMPONENT AND CLADDING PRESSURES FOR THE
 EXTERIOR DOORS AND WINDOWS ON THE PLANS APPEAR TO BE
 HIGHER THAN REQUIRED. FBCR 301.2.1.1 ALLOWS THE WIND
 SPEED TO BE CONVERTED TO NOMINAL WIND SPEEDS VASD WHEN
 THEIR TEST STANDARDS ARE BASED ON THE NOMINAL WIND
 SPEEDS.
  
 3) THE MAXIMUM DESIGN PRESSURES ON THE PRODUCT APPROVAL
 FOR THE OVERHEAD GARAGE DOOR ARE LOWER THAN THE
 REQUIRED DESIGN PRESSURES SPECIFIED ON THE PLANS.
 PLEASE CORRECT. FBCR 301.2.1
  
 4) FBCR 803.2.3.1 REQUIRES THE ROOF SHEATHING TO BE
 FASTENED WITH 8D RING SHANK NAILS AT 6" O.C. & IF THE
 ROOF FRAMING HAS A SPECIFIC GRAVITY OF 0.42 TO 0.49 THE
 FASTENING SPACING SHALL BE 4 INCHES ON CENTER IN ROOF
 ZONE 3.
  
 5) SUBMIT TWO SETS OF ENERGY CALCULATIONS FOR THE
 DWELLING. FBC ENERGY 401.2
  
 6) PROVIDE A BUCK DETAIL FOR THE 9' X 7' OVERHEAD
 GARAGE DOOR ON THE PLAN. FBCR 612.10.2.1 SPECIFY HOW
 THE 2 X 6S ARE ATTACHED TO THE STRUCTURE.
  
 7) SUBMIT PRODUCT APPROVALS FOR ALL OF THE CONNECTORS
 AS REQUIRED BY DCA RULE 9N-3 OR SPECIFY THE FLORIDA OR
 MIAMI-DADE PRODUCT APPROVAL NUMBERS IN THE
 ANCHOR/CONNECTOR SCHEDULE. THE PRODUCT APPROVAL NUMBERS
 ARE NOT PROVIDED. THE MIAMI DADE NOA NO. OR THE STATE
 FL # IS REQUIRED.
  
 8) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE
 STRUCTURAL WINDOW MULLIONS AS REQUIRED BY DCA RULE
 9N-3.
  
 9) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT.
  
 10) THE WINDOW TYPES ARE NOT IDENTIFIED ON THE PLANS.
 FROM THE DRAWINGS IT APPEARS THAT ALL OF THE WINDOWS
 ARE SINGLE HUNG. PRODUCT APPROVALS WERE SUBMITTED FOR A
 FIXED WINDOW. PLEASE IDENTIFY THIS WINDOW ON THE PLANS.
 CITY AMENDMENTS 107.2.1
  
 11) THE INFORMATION THAT WAS SUBMITTED FOR THE SINGLE
 HUNG WINDOWS AND THE DOORS DOES NOT HAVE THE FLORIDA OR
 MIAMI DADE PRODUCT APPROVAL ON THEM. PLEASE PROVIDE THE
 SHEETS WITH THIS INFORMATION SO THAT THEY CAN BE
 VERIFIED. DCA RULE 9N-3.
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]